11.10. DYNAMIC SET POINT

The regulator can be used to modify the
set point automatically, in accordance
with
the
outside
conditions.
modification is achieved by subtracting
a value from the set point; this value
depends on the outside air temperature
measured by probe S2.
The binary parameter H33=1-0 can be
used to enable/disable the Dynamic set
point function.
The dynamic set point is only active in
HP operation mode.
The following parameters need to be
defined for the dynamic set point:
H34
Balancing
line
between 0.5 and 2)
H35 Outside air temperature above
which
balancing
begins
between 15 and 25)
H36 Range of outside air on which
the
set
point
functions
between 5 and 10)
EXAMPLE:
When the set point is enabled (H33=1), three situations may arise:
-1st Case T.air <= H35 In this case the dynamic set point = Ut1
-2nd Case H35 < T.air < (H35+H36) In this case the dynamic set point = Ut1-[(T.air-H35)*H34]
-3rd Case T.air > (H35+H36) In this case the dynamic set point = Ut1-[H36*H34]
This
tilt
(value
(value
(value
H01=60° max. set point depending on HP
H34=1 balancing line tilt (45°)
H35=20°C temperature of the air at the start of balancing
H36=10°C range of the air on which the set point functions
for T.air <= 20°C we have ---> Set point = Ut1=60°C
for T.air = 23°C we have ---> Set point = Ut1-[(23 - H35)
for T.air >= ( H35 + H36 ) we have ---> Set point = Ut1-[ H36
outside air
H34]= 57°C
*
H34]=50°C
*