en
10.7
Application and function of CIF
module
11
Device settings
196
Device settings
3.
"Wilo Net termination".
Possible selection:
Wilo Net termination
Switched on
Switched off
After termination is done, an individual Wilo Net address is assigned to the pumps:
In the
"Settings" menu, select
1.
"External interfaces"
2.
"Wilo Net setting"
3.
"Wilo Net address" and assign an address (1-11) to each pump.
Double pump example:
▪ Pump head left (l)
– Wilo Net termination: ON
– Wilo Net address: 1
▪ Pump head right (II)
– Wilo Net termination: ON
– Wilo Net address: 2
Example with Multi-Flow Adaptation featuring four pumps:
▪ Primary pump
– Wilo Net termination: ON
– Wilo Net address: 1
▪ Pump secondary 1:
– Wilo Net termination: OFF
– Wilo Net address: 2
▪ Pump secondary 2:
– Wilo Net termination: OFF
– Wilo Net address: 3
▪ Pump secondary 3:
– Wilo Net termination: ON
– Wilo Net address: 4
Depending on the inserted CIF module type, an associated settings menu is displayed in
the menu:
"Settings"
1.
"External interfaces" displayed.
The respective settings are described in the display and in the CIF module documenta-
tion.
General settings are made under "Settings"
Description
Terminating resistor of the pump is
switched on.
If the pump is connected at the end of the
electrical bus line, "Switched on" must be
selected.
The pump's terminating resistor is
switched off.
If the pump is NOT connected at the end
of the electrical bus line, "Switched off"
must be selected.
, "Device settings".
WILO SE 2018-11