en
178
Double pump operation
Settings
Set auto control
Settings assistant, setpoints, options
Manual operation
Manual override
Double pump operation
Set double pump
External interfaces
Analogue, digital, SSM, SBM ...
Fig. 60: Menu double pump operation
Menu "Double pump function"
When a double pump connection is established, the "Double pump function" menu is
used to switch between
▪ Main/standby operation and
▪ Efficiency-optimised peak-load operation (parallel operation)
.
NOTICE
When switching the double pump function, different parameters of the pump are
fundamentally changed. The pump is then started automatically.
Menu "Pump cycling interval"
If a double pump connection is established, the time interval can be set in the "Pump
cycling interval" menu. Time interval: between half hour and 24 hours.
Menu "Connecting double pump"
If double pump connection is not yet established, in the "Settings" menu
1.
"Double pump operation"
2.
"Connecting double pump".
When the Wilo Net connection is established (see "Wilo Net" section), a list of available
and appropriate double pump partners will appear under "Connecting double pump".
Appropriate double pump partners are pumps of the same type.
When the double pump partner is selected, the display of this double pump partner is
switched on (Focus mode). In addition, the blue LED will flash to identify the pump.
NOTICE
Different parameters of the pump are fundamentally changed when creating the
double pump function. The pump is then started automatically.
Menu "Disconnect double pump"
When a double pump function is established, it can also be separated. Select "Discon-
nect double pump" in the menu.
NOTICE
When separating double pump function, different parameters of the pump are fun-
damentally changed. The pump is then started automatically.
Settings of
double pump operation,
addressing of
double pump partner,
mode etc.
, select
WILO SE 2018-11