configuration of the RS485 link
RS485 link interface
NB: the micro switches (SA3-X and
SA2-X) are in the open position when
SineWave™ is delivered.
polarisation
Usage and logic require the master
device of the network to polarise the
line (Rp resistances).
matching
Matching (Ra resistances) must be
performed at both ends of the line.
To avoid non-matching of the line when
disconnecting an end device you
should provide one or two matching
caps.
TM
SineWave
is a " slave " device.
However its RS485 link interface can
be polarised and matched in all the
chosen connection topologies either via
an external connector or via micro
switches on SineWave's MERY board.
4