4.5 MAINTENANCE POSITION
To access the nozzle, do the following:
Undo the wires (4) from the control box, the
flame detector (5) and undo the nut (3) from
the pump.
Loosen the screws (2) and extract the nozzle
holder assembly (1) by turning to the right.
Remove the small cables (4) from the elec-
trodes, loosen the screw (3, fig. 10, page 7)
and remove the diffuser disc-holder assembly
(7) from the nozzle-holder assembly (1).
Screw up the nozzle (6) holding the nozzle
support with a spanner.
Refit following the operations in the reverse
order to the one described above.
ATTENTION
During the reassembly of the nozzle-holder as-
sembly screw the nut (3) as shown in the figure
below.
Fig. 12
TIGHTEN WITHOUT MOVING
BACKWARDS TO THE END
4.6 COMBUSTION HEAD ADJUSTE-
MENT,
(see fig. 13)
The adjustment of the combustion head varies
depending on the burner output.
Do the following to adjust it:
Rotate the setting screw (8) clockwise or counter-
clockwise until the set-point marked on the regu-
lating rod (9) is level with the outside plane of the
nozzle-holder assembly (1).
In the example the regulating rod (9) is set at
notch 3; this means that the burner is regulated
for an output of 9 Kg/h with pump pressure at
12 bar and with the use of a nozzle of 2.25 GPH,
as indicated in the reference table.
4.7
AIR DAMPER ADJUSTMENT,
(see fig. 13)
To regulate the air damper, do the following:
Loosen the nut (10) and set the air damper by
turning the screw (11).
When burner shuts down the air damper automat-
ically close still a max. chimney depressure of 0.5 mbar.
When the adjustment is completed do the nut (10) up again.
3280
3
D5684
4
2
5
6
3
Fig. 13
8
GB
Fig. 11
1
7
8
9
E9317
11
10
1