3.4 ELECTRICAL WIRING

D4684
230V ~ 50Hz
A
3280
Main switch
CONTROL BOX, (see fig. 9)
To remove the control box from the burner it is necessary to:
disconnect all the connectors, the 7-pin plug, the high voltage cables
and the earth wire (TB);
unscrew the bolt (A) and pull the control box in the direction of the
arrow.
Fig. 9
To install the control box it is necessary to.
screw the bolt (A) in at a torque of 1 - 1.2 Nm;
reconnect all the connectors previously disconnected.
NOTES:
The burners have been type-approved for intermittent operation.
This means they must stop at least once every 24 hours in order to al-
low the electrical control box to check its efficiency on start-up.
The boiler limit thermostat (TL) normally ensures the burner halts. If
this does not happen a time switch halting the burner at least once
every 24 hours must be applied in series to (TL).
E9275
ATTENTION:
Do not swap neutral and phase over, follow the diagram
shown carefully and carry out a good earth connection.
The section of the conductors must be at least 1mm . (Un-
less requested otherwise by local standards and legislation).
The electrical wiring carried out by the installer must be in
compliance with the rules in force in the country.
TESTING
Check the burner stops by opening the ther-
mostats.
Check the burner stops by shading the
flame detector.
CARRIED-OUT
IN FACTORY
TO BE DONE BY
THE INSTALLER
6
GB
4
KEY TO LAY-OUT:
– Capacitor
C
– Electrode
E
– Flame detector
F
– Hour counter
h1
– Motor
MV
– Bridge socket
P
RS
– Remote reset
SER – Safety lockout device
– Lock-out signal
S3
(230V - 0.5 A max)
T6A – Fuse
– Burner-earth
TB
– Limit thermostat
TL
– Safety thermostat
TS
– Oil valve
V1
– Safety lockout device
V2
– 7 pin plug
X7
XP7 – 7 pole socket