If the wall on which the sensor is to be installed is made of highly
heat-absorbing material (e.g. concrete, brick, etc.), or of hardened
glass, the sensor may be installed in the ceiling at a distance from
the heater, according to Figure 6.
1
1
Figure 6: Sensor installation on ceiling on centreline of heater as
seen from the front and side
1.
300 mm
Positioning the heater - recess installation
To position the sauna heater in a recess:
1.
Position the heater at a safe distance from the fl oor, side
walls and interior fi ttings (see Figure 7).
2.
Position the sensor according the picture (see Figure 7).
2
3
1
1
5
3
Figure 7: Positioning the heater - recess installation
1.
Minimum distance from side wall:
Sense Commercial 6-8: 110 mm
Sense Commercial 10-16-20: 350 mm
2.
Sensor position alt 1:
Sense Commercial 6-8: 300 mm from heater
Sense Commercial 10-16-20: 500-1500 mm from heater
3.
Sensor
4.
Max. 1000 mm
5.
Sensor position alt 2:
Sense Commercial 6-8: 300 mm from heater front
Sense Commercial 10-16-20: 500-1500 mm from heater
front
6.
Sensor position:
6A. Sense Commercial 6-8: 150 mm from ceiling
6B. Sense Commercial 10-16-20: 1500 mm from fl oor
7.
Minimum distance from ceiling:
Sense Commercial 6-8: 1030 mm
Sense Commercial 10-16-20: 1270 mm
8.
Minimum distance from interior fi ttings:
Sense Commercial 6-8: 100 mm
Sense Commercial 10-16-20: 400 mm
9.
Minimum ceiling height:
6A
7
8
9
4
6B
11
10
12
Sense Commercial 6-8-10: 1900 mm
Sense Commercial 16-20: 2100 mm
10. Minimum distance: 20 mm
11. Minimum distance from interior fi ttings:
Sense Commercial 6-8: 30 mm
Sense Commercial 10-16-20: 200 mm
12. Distance from fl oor: 270 mm (Sense Commercial 6-8 with
legs: 100 mm)
Positioning the control panel (Pure, Elite)
The control panel must be correctly positioned with regard to
safety distances.
Figure 8: Safety distance, control panel Pure, Elite
1.
Heater
2.
Control panel
3.
Max. 900 mm
4.
Min. 300 mm
Positioning the inlet vent
Install the inlet vent straight through the wall under the centreline
of the heater.
Vent size for a family sauna approx. 125 cm².
The air circulation from the door must concord with the hot air
circulation from the heater.
1
3
Figure 9: Positioning the air intake and exhaust vents
1.
Inlet vent position.
2.
Outlet vent position through the sauna wall.
3.
Outlet vent position through the cavity.
4.
Outlet vent position via duct.
4
2
3
1
2
4
15