Télécharger Imprimer la page

Hauff-Technik HSI150 DG Notice De Montage page 16

Publicité

Les langues disponibles
  • FR

Les langues disponibles

HSI150 DG for retrofitting
• The marking lines on the adapter ring must
match the arrows marked on the wall insert
(see Fig.: 10).
• The recesses from the adapter ring must lock
over the bayonet of the wall insert.
• The sealing surface of the adapter ring must
be smooth and plain inside the wall insert.
Measure the diameter of the cables using a sliding
7
caliper (see Fig.: 11).
Then select the segmented ring of a press seal
8
section according to the measured diameter of the
cables (diameter range is visible on the segments in
the detail drawing), cut into the sectioning point
using the knife provided and pull section away (see
Fig.: 12).
You must then repeat this step in exactly the same
way at the remaining segments of the press seal
sections; the number of segments removed
must be identical at all press seal sections.
Then, only lubricate the cutting surfaces and cable
9
sealing surfaces of the press seal using GM lubricant
(delivery package) (see Fig.: 13).
Do not lubricate the outer sealing surface of
the press seal (see Fig.: 14)!
Fasten the press seal over the cables and push it
10
flush against the outside edge of the adapter ring
(see Fig.: 15).
The outer sealing surface of the press seal and
the inner surface of the adapter ring must be
free of lubricant and dry (clean with cleaning
cloth provided).
Unassigned openings of the press seal HSI150 DG
11
3x24-54 or respectively HSI150 DG 6x10-36 must
be sealed with the supplied sealing plugs (see Fig.:
16).
Blind sealing plug opening must point in direction
of installation.
Finally, tighten all of the screws (Allen key size
12
WAF 5) of the press seal with the extension in
a crossover pattern until the specified torque is
reached (table 1).
For the HSI150 DG 6x10-36 press seal, first slightly
tighten the screws of the middle press plate, then
slightly tighten both of the outer press plates. Con-
tinue to do this alternately until the specified torque
(table1) is reached.
Once all of the cables have been laid, check the
torque at the press seal and tighten if necessary.
Art. Nr.: 5090032033
Rev.: 05/2020-04-28
EN
15

Publicité

loading