Operating Instructions
Technical data
Reference conditions (as per IEC 61298-1)
Ambient temperature
Air pressure
Air humidity
Auxiliary energy
Installation position
Application conditions
Permitted
Temperature ranges
Vibration resistance
Shock resistance
Mechanical service life
Enclosure rating
Installation position
Contamination rating
Air humidity
UV radiation
O P E R A T I N G I N S T R U C T I O N S P B S p l u s
6 2
15 ... 25 °C (59 ... 77 °F)
860 ... 1,060 mbar (12.5 ... 15.4 psi)
45 ... 75% r.h.
DC +24 V
Calibrated with vertical installation with the process connection pointing downwards
Measuring material: –20 ... +85 °C (–4 ... +185 °F)
Environment: –20 ... +80 °C (–4 ... +176 °F)
Storage: –20 ... +70 °C (–4 ... +158 °F)
Nominal temperature: 0 ... 80 °C (32 ... 176 °F)
20 g, 10 ... 2,000 Hz (IEC 60068-2-6, with resonance)
50 g, 6 ms (IEC 60068-2-27, mechanical)
100 million load changes (10 million load changes for measuring ranges > 600 bar (8,702 psi)
IP65 and IP67
The enclosure ratings specified (as per IEC 60529) apply only with mating plugs of the corre-
sponding enclosure rating when plugged in.
Flexible
max. 3
≤ 45 ... 75% r.h.
At high ambient temperatures and high UV radiation, the pressure switch must be installed with
additional shading to prevent damage to the digital display and pushbuttons.
9. TECHNICAL DATA
PBS plus
8024946 | SICK AG
Subject to change without notice