SICK PBS plus Notice D'instruction page 48

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Operating Instructions
Menu item
Description
AVGD
Attenuation (digital display)
AVG1 / AVG2 Attenuation (switching output 1 / 2)
AVG3
Attenuation (analog signal)
UNIT
Unit switchover
Zero point adjustment / "Auto-zero"
0SET
version (max. 3% of the range)
DISM
Display value in display mode
DISU
Update rate (digital display)
DISR
Turn display 180° (digital display)
DRES
Resolution (digital display)
Delete memory (min/max system
RHL
pressure)
PAS
Password entry
TAG
Measurement device name (TAG)
O P E R A T I N G I N S T R U C T I O N S P B S p l u s
4 8
5. COMMISSIONING, OPERATION
Parameter
0.00 ... 65.00 s
0.00 ... 65.00 s
0.00 ... 65.00 s
BAR, mBAR, MPA, KPA, PSI, KGcm (kg/cm²), % Order-related
Yes / No
ACT = Current system pressure
LOW, HIGH = Min/Max system pressure
OFF = Display off
SP1 / FH1 = Set threshold value
RP1 / FL1 = Set threshold value
SP2 / FH2 = Set threshold value
RP2 / FL2 = Set threshold value
1, 2, 5, 10 updates/second
Yes / No
OPT = Optimized (stable measurement value
display with the rounding factor of the last
digit optimized to the measuring range)
FULL = Maximum (finest resolution, an attenu-
ation of the digital display might have to be
set for a stable measurement value display)
Yes / No
0000 = No password, password entry digit
by digit
32 selectable characters (A–Z ‚0 ... 9; - ‚EMPTY)
(2 spaces in a row end entry and causes this
and the character behind it to be deleted)
PBS plus
Factory setting
0.20 s
0.00 s
0.00 s
ACT
5
OPT
0000
without
8024946 | SICK AG
Subject to change without notice

Publicité

Table des Matières
loading

Table des Matières