INSTALLATION MENU

From the Standard Display press the ENTER plus the DOWN key for 3 seconds to enter the Installation Menu: the first parameter will be displayed, the value in the large digits and its
name in the small digits. To modify the parameter value press the ENTER key, the value will flash, press the UP or DOWN key to modify the value and confirm by pressing the ENTER key
again. To scroll through the menu press the UP or DOWN keys.
NAME
SPL
Minimum Set Point value
Increments of 1º
SPH
Maximum Set Point Value
Increments of 1º
diF
Set points differential
Once the setpoint temperature has been reached, and while the temperature remains between diF ºC/ºF above or below the setpoint, there is no demand for
transfer of heat or cold, and the unit remains in null mode. Increments of 1º.
SSC
Soft Start Cycles (ON/OFF)
Programmable soft start for the road compressor clutch.
dit
Defrost initiation timer (minutes)
Increments of 30 minutes.
On time out the unit will switch from cool to the appropiate defrost mode. The timer will count all the time the system is in any cool mode. The timer will be reset
when a defrost starts.
When the value is set at 0, is the test position: the defrost will begin in 15 seconds.
dtt
Defrost termination timer (minutes)
Increments of 5 minutes.
Timer will count from defrost mode initiation. Timer will reset after a temperature defrost termination or timer time out. On time out the unit will switch from defrost
to null mode.
When the value is set at 0, is the test position: the defrost will stop in 15 seconds.
EFc
Evaporator Fans constant blow
on: evaporator fans stays on also during null mode.
off: evaporator fans cycles on and off with the regulators.
In-Cab Control Box
DESCRIPTION
Eng
DEFAULT
MIN
MAX
-32 ºC
-32 ºC
SPH
(R-404A)
-20 ºC
(R-134a)
22 ºC
SPL
38 ºC
3
1
5
OFF
OFF
ON
240
30
480
30
5
50
OFF
OFF
ON
28