6.1

SETTING DATE AND TIME

Date and time may be set via the CLOCK menu.
CLOCK SETTING
DD-MM-YY
Setting the current date and time correctly
The correct setting of the date and time is essential for the recording of the event log.
6.2

DISPLAY LANGUAGE SETTING

The table below shows the languages which can be set for the display.
Parameter
LANGUAGE
The parameters are changed via the arrow buttons (
button is used to confirm the entry.
6.3

NEW BATTERY INSTALLATION

The NEW BATTERY INSTALLATION menu is used in case battery circuit breaker BCB is not
closed, when requested, in the start-up phase. In this case the system will start considering the
battery completely discharged and activating the alarm "A10 – BATTERY FAULT".
To set the battery autonomy to 100% it is necessary to access the menu and press the
button to confirm.
6.4

BATTERY CONFIGURATION

In case the UPS has been tested without knowing the characteristic data of the storage
battery, the BATTERY CONFIGURATION menu allows to set such data. In particular, the
following data can be set:
 Battery capacity in Ampere-hours (Ah)
 Recharging current in Amperes (A)
 Nominal autonomy in minutes
Manuel de l'utilisateur de l'UPS
The single digits can be modified via the arrow
keys (
hh : mm
(ENTER).
Range
ITALIAN
GERMAN
FRENCH
ENGLISH
PORTUGUESE
SPANISH
POLISH
TURKISH
UPS user manual
Utilizzo dell'UPS
/
) and confirmed by pressing
/
) to increase the digits, and the
OMD10074 REV. C
29

Publicité

Table des Matières
loading

Table des Matières