Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
Alarm
Description
Possible
causes
Solutions
48
OMD10074 REV. C
UPS user manual
Manuel de l'utilisateur de l'UPS
Utilizzo dell'UPS
A25
INVERTER OFF
The inverter is blocked due an operation failure.
 Various.
1. Reset the system.
2. If the alarm persists, contact our Technical Support Service.
A26
COMMUNIC ERROR
Internal error.
 Microcontroller communication problems.
1. If the alarm persists, contact our Technical Support Service.
A27
EEPROM ERROR
The controller has detected an error in the parameters stored in
2
E
PROM.
 Wrong parameters entered during programming.
1. Contact our Technical Support Service.
A28
CRITICAL FAULT
An alarm has been activated which causes the shutdown of part of the
UPS (rectifier, inverter, static switch).
 System failure.
1. Check which alarms are present and carry out the indicated
procedures.
2. If the alarm persists, contact our Technical Support Service.
A29
MAINTENANCE REQ
It is necessary to carry out maintenance work.
 The time limit since the last maintenance work has elapsed.
1. Contact our Technical Support Service.