Les langues disponibles

LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
UPS user manual
Manuel de l'utilisateur de l'UPS
Utilizzo dell'UPS
AC line on rectifier input within tolerance
GREEN
Wrong phase rotation
GREEN
AC mains failure on rectifier input
OFF
AC bypass line within tolerance
GREEN
Wrong phase rotation
GREEN
AC bypass line out of tolerance
OFF
AC bypass line failure
Rectifier off or faulty
GREEN
DC voltage out of tolerance
RED
Rectifier on and DC voltage within tolerance
GREEN
circuit breaker BCB closed and battery charging
GREEN
Battery discharging or under TEST
GREEN
Circuit breaker BCB open
ORANGE
Battery fault (following a battery test)
RED
Battery not available
OFF
Inverter voltage within tolerance and static switch
GREEN
closed
Inverter overload or short-circuit
GREEN
Inverter off or voltage out of tolerance
OFF
Re-transfer blocked
ORANGE
Static bypass switch closed
ORANGE
Static bypass switch open
OFF
Output circuit breaker OCB closed
GREEN
Output circuit breaker OCB open
OFF
Manual bypass switch MBCB closed
ORANGE
Manual bypass switch MBCB open
OFF
Emergency power off (EPO) activated
RED
Normal operation
OFF
Maintenance request (slow flashing)
ORANGE
Critical alarm (fast flashing)
ORANGE
Normal operation
OFF