A53
FIRMWARE ERROR
The controller has detected an incompatibility in the control software.
 The software update was not performed properly.
1. Contact our Technical Support Service.
A54
CAN ERROR
Internal error.
 Microcontroller communication problems.
1. Contact our Technical Support Service.
A55
PAR CABLE DISC
Parallel cable doesn't communicate.
 Parallel cable disconnected or damaged.
1. Check the connection of cable
2. Contact our Technical Support Service.
A56
MAINS UNBALANCE
The rectifier input voltage is unbalanced.
 Problems on the LV or MV distribution network
 Defect of the measuring circuit
1. Check the input voltage
2. Contact our Technical Support Service.
A63
START SEQ BLOCK
During the UPS start-up a failure prevented the proper execution of the
sequence.
 Control devices in wrong position or operated improperly.
 Possible internal fault.
1. Make sure the position of the control devices (isolators, selectors)
is as specified in the procedures (see "Installation and start-up"
section).
2. If the alarm persists, contact our Technical Support Service.