MISE EN SERVICE
5
Only for signal
Only for signal
Only for signal
Only for signal
2. String comparison
converters with
converters with
Afterwards you must compare the strings. This is to check the string display. Confirm that the two
converters with
converters with
SIL-
SIL-
SIL-
SIL-
strings are identical. The verification texts are displayed in German and in English with any other
qualification
qualification
qualification
qualification
menu language.
Lock
3. Serial number confirmation
adjustment /
Then confirm that the serial number of your device has been properly transferred. This checks for
Unlock
proper device communication.
adjustment
4. Parameter verification
All safety-relevant parameters must be verified following a change:
•
SIL parameter 1: Zero adjustment
•
SIL parameter 2: Slave in/out
•
Non-SIL parameter 1: Display of measured value
•
Non-SIL parameter 2: Display value 1, unit of application
•
Non-SIL parameter 3: Display value 1, unit of application
•
Non-SIL parameter 4: Backlight
Confirm the changed values one after the other
If configuration as described has been completely and correctly carried out, the device is locked and
ready to operate.
Otherwise the device remains unlocked and thus in an unsafe state.
As long as the device is supplied with power, the display and adjustment module remain in the
momentarily set operating menu. There is no automatic, time-controlled jump back into the display of
measured values.
Tableau 5-1: Comissioning
1 Only available for electronic differential pressure when the slave sensor is activated
5.6.2 Display
Menu language
In this menu item you can set the desired language.
Factory settings: English
German, English, French, Spanish, Portuguese, Italian, Dutch, Russian, Turkish, Polish and Czech.
Displayed value
In this menu item you can define how the measured value should be presented on the display.
1 and 2
The factory setting is "Linear percent".
Process pressure
Level
Differential pressure 1
Density 1
Interface 1
Backlight
A backlight on the display is available, which can be turned on or off in this menu. By default, this
function is disabled.
Off, On
Tableau 5-2: Display
1 Only available for electronic differential pressure when the slave sensor is activated
60
Process pressure, Percent, Scaled, Current
output, Linear percent, Meas. cell temp. and
Electronics temperature.
Filling height or Pressure (Adjustment units),
Static pressure, Percent, Scaled, Current output,
Linear percent, Meas. cell temp. and Electronics
temperature
Differential pressure, Static pressure, Percent,
Scaled, Current output, Linear percent, Meas.
cell temp. and Electronics temperature
Density, Differential pressure, Percent, Scaled,
Current output, Linear percent, Meas. cell temp.
and Electronics temperature
Interface height, Differential pressure, Percent,
Scaled, Current output, Linear percent, Meas.
cell temp. and Electronics temperature.