Info; Reset - KROHNE OPTIBAR PM 5060 C Manuel De Référence

Masquer les pouces Voir aussi pour OPTIBAR PM 5060 C:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

OPTIBAR PM 5060 C

5.6.5 Info

Nom de l'appareil
Modèle de l'appareil
Etalonnage usine
Caractéristiques
capteur

5.7 Reset

The reset function resets specific user entries. There are 2 reset functions available:
Delivery status
Delivery status
Delivery status
Delivery status
Restore the default values at the time of delivery, including the order-specific settings. A false
signal suppression, user programmable linearization curve as well as the measured value
memory will be deleted.
Basic settings
Basic settings
Basic settings
Basic settings
Reset the set data, including special parameters to the default values of the manufacturer. A
false signal suppression, user programmable linearization curve as well as the measured value
memory will be deleted.
The safety-relevant menu items defined as functional safety according to IEC 61508 (Edition 2)
are marked with (SIL).
The following menu items are affected during a reset
Menu item
Measurement loop name
Slave for electronic differential
pressure
Application (SIL)
Unit
Sensor mounting correction (SIL)
Adjustment (SIL)
Damping (SIL)
Current output (SIL)
Lock adjustment (SIL)
Simulation
01/2021 - 4004819802 - MA OPTIBAR PM 5060 C R04 fr
Nom de l'appareil
Numéro de série
Version du logiciel
Version de matériel
Date d'étalonnage usine
Date de dernière modification
Caractéristiques appareil selon commande
Parameter
Slave for electronic differential
pressure
Application
Adjustment units
Temperature unit
Zero / Min.-adjustment
Span / Max.-adjustment
Integration time
Current output mode
Current output variable
Current output adjustment
Current output min./max.
www.krohne.com
MISE EN SERVICE
Standard value
Sensor
disabled
Level
mbar (cell ≤ 400 mbar)
bar (cell ≥ 1 bar)
°C
0.00 bar
0.00 bar - 0.00%
+URL in bar - 100%
0.0 seconds
Output characteristic 4...20 mA
Failure mode ≤ 3.6 mA
Linear percent - Level
0...100% = 4...20 mA
Min. 3.8 mA
Max. 20.5 mA
Unlock
Process pressure
5
63

Publicité

Table des Matières
loading

Table des Matières