OPTIBAR PM 5060 C
Damping
For the damping of process-dependent measured value fluctuations, you can choose a suitable
integration time. The values which can be entered are from 0 ... 999 seconds with an increment of 0.1
seconds.
Integration time
Linearisation
A linearisation is necessary for all vessels in which the volume does not increase linearly with the
level height, e.g. in a horizontal cylindrical or spherical tank, and the indication or output of the
volume is required. Corresponding linearisation curves are preprogrammed for these vessels. They
represent the correlation between the level percentage and vessel volume. By activating the
appropriate curve, the volume percentage of the vessel is displayed correctly. Enter the desired
parameters using the function buttons and save the entries. Note the following if the pressure
transmitter with corresponding approval is used as part of an overfill protection system according to
WHG (Water Resources Act): If a linearization curve is selected, the measuring signal is no longer
linearly proportional to the level. This must be taken into consideration by the user, particularly when
setting the switching point on the limit switch.
Type of linearisation
Current output
In the current output menu, the saturation region for above or below a threshold is set. Under
"Current output min./max." these limit values can be set. The factory setting is 3.8 mA and 20.5 mA.
This corresponds to the NAMUR recommendation NE 43.
Mode
Min. and
Max.
Lock
In this menu item, a 4-digit PIN can be activated, which protects against undesirable or unintended
adjustment /
changes of the settings. With a PIN active, remote access via software or other systems is also no
Unlock
longer possible.
adjustment
Run now
Only for signal
Only for signal
With this menu item you can protect the sensor parameters from unwanted or unintended changes.
Only for signal
Only for signal
converters with
converters with
converters with
converters with
To avoid possible errors during parameter adjustment in unsafe operating environments, a
SIL-
SIL-
SIL-
SIL-
verification procedure is used that allows parameterization errors to be reliably detected. Safety-
qualification
qualification
relevant parameters must be verified before they are saved to the device. In addition, to protect
qualification
qualification
Lock
against unwanted or unauthorised adjustment, the device is locked in normal operating state against
adjustment /
any parameter changes.
Unlock
1. Enter PIN
adjustment
Start-up - Lock adjustment - Unlock -
The device is shipped in locked condition. The PIN in delivery status is "0000".
01/2021 - 4004819802 - MA OPTIBAR PM 5060 C R04 fr
Output characteristic
Failure mode
Min. current
Maximum current
www.krohne.com
MISE EN SERVICE
In 0.1 second increments.
Level
Level
Level
Level
Linear, Horiz.cylinder, Sphere and User
programmable.
0...100% = 4...20 mA or
0...100% = 20...4 mA
≤ 3.6 mA, ≥ 21 mA, last valid measured
value
3.8 mA, 4 mA
20.5 mA, 20 mA
5