MISE EN SERVICE
5
Check function
Code
Text message
C700
Simulation Active
Out of specification
Code
Text message
S600
Impermissible electronics
temperature
S603
Impermissible operating
voltage
S605
Pressure value out of
specification
Only for signal converter with SIL-qualification
Only for signal converter with SIL-qualification
Only for signal converter with SIL-qualification
Only for signal converter with SIL-qualification
If measured values are outside of the specification and an "Out of Specification" message is
triggered, this message results in:
• Status message "Failure"
• Fault signal via the current output

Maintenance required

Code
Text message
M500
Error with the reset delivery
status
M501
Error in the non active
linearisation table
M502
Error in the event memory
M504
Error on a device interface
M507
Error in the device settings
68
Cause
A simulation is active
Cause
Temperature of the
electronics in the non-
specified section
Operating voltage below
specified range
Measured process pressure
below or above the setting
range
Cause
Saved reset delivery status
is incorrect
Index markers are not
continuously rising, for
example illogical value
pairs
Hardware error in EEPROM
Hardware defect
Error during setup
Error when carrying out a
reset
www.krohne.com
Action or description
Finish simulation
Wait for automatic end after
60 minutes
Action or description
Check ambient temperature
Isolate electronics
Use device with higher
temperature range
Check electrical connection
- if necessary, increase
operating voltage
Check the nominal range of
the device
If necessary, use a device
with a higher measuring
range
Action or description
Send device for repair
check the linearization
table,
Delete table/Create new
Exchange the electronics
Send device for repair
Check connections
Exchange the electronics
Send device for repair
Repeat setup,
Repeat reset
01/2021 - 4004819802 - MA OPTIBAR PM 5060 C R04 fr
OPTIBAR PM 5060 C
DevSpec State in CMD 48
"Simulation Active" in
"Standardised Status 0"
DevSpec State in CMD 48
Bit 23-0 of byte 14...24
Bit 23-1 of byte 14...24
Bit 23-2 of byte 14...24
DevSpec State in CMD 48
Bit 0 of byte 14...24
Bit 1 of byte 14...24
Bit 2 of byte 14...24
Bit 3 of byte 14...24
Bit 4 of byte 14...24