Adjustment density
Figure 5-6: Adjustment density
1 Sensor mounting correction
Sensor mounting correction
Sensor mounting correction
Sensor mounting correction
In this menu item you compensate the influence of the installation position of the device (offset) on the measured va-
lue.
2 Distance min. - max.
Distance min. - max..
Distance min. - max.
Distance min. - max.
Enter the distance between both measuring points.
3 Min.-adjustment
Min.-adjustment
Min.-adjustment
Min.-adjustment
Enter the (pressure) value for the min. density.
This corresponds to the output signal of 4 mA.
4 Max.-adjustment
Max.-adjustment
Max.-adjustment
Max.-adjustment
Enter the (pressure) value for the max. density.
At 100% this corresponds to the output signal of 20 mA.
Adjustment interface
Figure 5-7: Adjustment interface
1 Sensor mounting correction
Sensor mounting correction
Sensor mounting correction
Sensor mounting correction
In this menu item you compensate the influence of the installation position of the device (offset) on the measured va-
lue.
2 Distance max./min.
Distance max./min.
Distance max./min.
Distance max./min.
Enter the distance between both measuring points.
3 Min.-adjustment
Min.-adjustment
Min.-adjustment
Min.-adjustment
Enter the (pressure) value for the min. position of the interface.
This corresponds to the output signal of 4 mA.
4 Max.-adjustment
Max.-adjustment
Max.-adjustment
Max.-adjustment
Enter the (pressure) value for the max. position of the interface.
At 100% this corresponds to the output signal of 20 mA.

5.6 Extended adjustment

The main menu is divided into five sections:
• Start-up
• Display
• Diagnosis
• Additional adjustments
• Info

5.6.1 Comissioning

Measurement
Assign a unique device ID. This is useful or even necessary in digital systems and for monitoring large
loop name
systems.
Application
Here you select the application: process pressure, level, differential pressure 1, density 1 and
interface 1 are available. The default setting is process pressure and the slave for electronic
differential pressure is deactivated.
01/2021 - 4004819802 - MA OPTIBAR PM 5060 C R04 fr
www.krohne.com
MISE EN SERVICE
5