Operating Instructions
Automatic Closing
A.switch.can.be.connected.across.terminals.A12 and.B12 (AUTO/WZL).in.order.to.activate.the.Automatic Closing function..
If.Automatic.Closing.is.activated,.the.door.is.closed.by.the.control.unit.after.the.automatic.closing.time.(time.Z4.=.60.s).has.
elapsed..If.the.Early.Warning.function.is.activated.(DIP.switch.1.6.in.the.ON.position),.before.commencing.the.automatic.clos-
ing.procedure.an.early.warning.is.given.by.actuating.relay.1.with.an.early.warning.time.Z3.=.3.s.
By.attaching.the.timer.module.to.system.plug.X1.of.the.ELS.Professional.Card.3.1,.the.reclosing.time.can.be.variably.set.be-
tween.2.and.240.s.
For.a.description.of.the.timer.module,.see.„Timer.Module.Technical.Information"
Photoelectric Barrier
A.photoelectric.barrier.can.be.connected.across.terminals.A7 and.B7 (LS)..For.installation.the.wire.jumper.across.terminals.
A7 and.B7 must.be.removed.
This.control.input.has.two.functions:
•. If.the.photoelectric.barrier.responds.during.downward.movement.(Stör2.lamp.flashes),.the.door.stops.instantly..After.an.
internal.time.of.0.5.s.(time.Z0).has.elapsed,.the.S80.opens.the.door.again..Depending.on.the.setting.of.DIP.switch.1.3,.
the.control.unit.moves.the.door.clear.of.the.obstacle.or.to.the.top.end.limit.
•. If.the.door.is.open.or.being.opened.and.the.light.beam.is.interrupted.and.then.released.again,.the.automatic.closing.time.
Z4.is.reduced.to.3.s.in.the.event.that.DIP.switch.1.8.is.in.the.ON.position..If.the.DIP.switch.1.8.is.set.to.OFF,.the.automatic.
closing.time.Z4.is.reset.
Safety Edge
The.following.safety.edge.systems.can.be.connected.to.door.control.unit.S80.directly:
•. Pneumatic.safety.edge.or
•. Electric.safety.edge.or
•. Optoelectronic.safety.edge:.FRABA.OSE
The.sensor.required.is.integrated.into.the.control.unit.(self-monitoring.sensor.as.per.pr.EN.12453)..The.pneumatic.safety.edge.
or.the.electric.safety.edge.is.connected.up.to.terminals.A6 and.B6.(SKS/USA)..To.ensure.that.the.spiral.rubber-insulated.
cable.is.monitored,.the.1.2.kΩ.resistor.clamped.across.terminals.A6.and.B6.is.supplied.with.the.unit..This.has.to.be.connected.
in.the.pressure.switch.contact.or.at.the.end.of.the.electrical.safety.edge.in.accordance.with.the.wiring.diagram.for.S80.
In.the.case.of.factory-assembled.electric.safety.edges,.check.their.terminating.resistance..Safety.edges.with.a.1.2.kΩ.or.8.2.
kΩ.terminating.resistor.may.be.used..Connect.the.OSE.optoelectronic.safety.edge.made.by.FRABA.to.terminals.A8,.A9.and.
B8.(OSE).direct.without.the.need.for.any.terminating.resistor.(A8.-.brown.wire,.A9 -.green.wire,.B8 -.white.wire)..To.adapt.the.
control.unit.to.the.respective.safety.edge,.set.DIP.switches.1.1,.2.1.and.2.2.according.to.the.following.table.
Type of safety edge
Safety.edge.1.2.kOhm
Safety.edge.8.2.kOhm
Electric.safety.edge.1.2.kOhm
Electric.safety.edge.8.2.kOhm
Optoelectronic.safety.edge.FRABA.OSE
Caution
When using optoelectronic safety edge FRABA OSE DIP switch 2.1 must always be set to the OFF position
or else the self-monitoring system of the sensor integrated into the control unit will be deactivated.
If a pneumatic switching rail is used, DIP switch 1.1 must be set to the ON position, as otherwise the func-
tion of the pneumatic rail will not be correctly monitored. It is possible that safety devices are bypassed
upon delivery. Please ensure that there are no forbidden bypasses prior to initial start-up.
If.the.safety.edge.responds.during.downward.movement.(bottom.rail.sensor.LED.SKS/USA.lights.up),.the.door.is.stopped.
instantly.by.the.S80.control.unit..After.an.internal.time.of.0.3.S..(time.Z2).has.elapsed,.the.S80.opens.the.door.again..Depend-
ing.on.the.setting.of.DIP.switch.1.3,.the.control.unit.moves.the.door.clear.of.the.obstacle.or.to.the.top.end.limit.
If.the.DIP.switch.1.1.is.set.to.ON,.the.bottom.switch-off.point.of.the.door.is.adjusted.once.the.door.contacts.the.floor.
34
DIP 1.1
DIP 2.1
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
OFF
DIP 2.2
ON
OFF
ON
OFF
OFF