Figure 25: LCS Tool - setting Time of Use
Procedure:
1. Open the LCS-Tool.
2. Log in as an Installer.
3. Call up the menu Setup.
4. In the Inverter Parameter menu in the Immediate
controls area, make sure that the parameter Active
Power (P_ref) is set to 100%.
5. Ensure that the Modbus parameter 40349
(WMaxLimPct) is set to 100%.
6. Enable the Time of Use function in the Power
Management menu. Otherwise, the Peak Load
Shaving function could be used.
7. To define the time windows of both periods, select the
period to be defined under Seasons and adjust the
corresponding settings: To define the entire day with
the same setting, select the field All Day of the
corresponding day of the week. The same setting is
Installation manual
valid for the power throughout the day. To make
settings for the individual periods, select the desired
periods of the corresponding day of the week.
8. Select the period to be used under Seasons.
9. Enter the power of the respective time interval. As a
result, the battery is discharged (Feed in), if needed, at
values with a positive sign (+), and charged (Charge)
at values with a negative sign (-).
10. Select [Save] to save the changes.
5 LCS-Tool
IMVIOBOX-IA-xx-17
27