Gossen MetraWatt Camille Bauer SINEAX V 604 Mode D'emploi page 22

Convertisseur de mesure universe
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Measuring output
Output signals A1 and A2
The output signals can be either load-independent DC
currents I
or DC voltages U
. The desired mode is set on DIP
A
A
switches and the setting range is programmed on a PC. A1
and A2 are not DC isolated and the same value is available
at both outputs.
Standard ranges for I
: 0...20 mA or 4...20 mA
A
External resistance I
: R
max. [kΩ] =
A1
ext
resp. =
I
= Full-scale output current value
AN
External resistance I
: R
max. [kΩ] =
A2
ext
Standard ranges
for U
:
0...5, 1...5, 0...10 or 2...10 V
A
Load capacity
[kΩ] ≥
U
/ U
:
R
A1
A2
ext
Power supply H
AC/DC power pack (DC and 45...400 Hz)
Table 2: Rated voltages and tolerances
Rated
Fuse
voltage U
N
24... 60 V
T 250 mA
DC / AC
85...230 V
1
T 100 mA
DC / AC
24... 60 V
T 160 mA
DC / AC
85...230 V
T 80 mA ± 15%
AC
85...110 V
T 80 mA – 15...+ 10%
DC
Power consumption: < 1.4 W resp. < 2.7 VA
Output contact K
The output contact can be used:
a)
as an additional means of signalling operation of the
open-circuit sensor supervision when the transmitter
is used in conjunction with resistance thermometers,
thermo-couples, resistance sensors and potentio-
meters.
b)
to monitor the measured variable in relation to a limit
or its rate-of-change where an additional means of
signalling operation of the open-circuit sensor
supervision (see "a") is considered unnecessary.
c)
to monitor the measured variable in relation to a limit
or its rate-of-change when measuring a DC voltage or
a current.
Note on a): The relay has to be activated by programming its
operating mode as "energised" or "de-
energised".
Available operating modes are:
"Output at last value, relay energised"
"Output at last value, relay de-energised"
"Output at setting, relay energised"
"Output at setting, relay de-energised"
22
15 V
I
[mA]
AN
– 12 V
I
[mA]
AN
0,3 V
I
[mA]
AN
U
[V]
A
20 mA
Tolerances
Instrument
version
DC – 15...+ 33%
Standard
AC ± 15%
(Non-Ex)
DC – 15...+ 33%
Type of
AC ± 15%
protection
Intrinsically
safety
[EEx ia] IIC
Relay pick-up/reset threshold:
1 to 15 kΩ, acc. to measuring mode and range
Note on b): The relay must be activated by programming:
"Output corr. to input variable, relay inactive"
The limit must also be programmed (see Section
"Limit")
Note on c): It is only necessary to program the limit (see
remarks on "b)" above)
Limit value
Limit value type:
Programmable
– for monitoring the input variable
in relation to a lower or upper limit
between –10 and + 110%
left side of Fig. 3)
or
– for monitoring the rate-of-change
of the input variable
Slope =
between ± 1 and ± 50%
right side of Fig. 3)
Hysteresis:
Programmable from 0.5 to 100%
or
1 to 100%
Operating and
resetting delays:
Programmable from 1 to 60 s
Input variable
limit
Upper
Lower
S
G
GW
H
H
GW
G
S
H hysteresis, GW limit value, G operation area, S failure area
Fig. 3
Light emitting diodes
(
(
Table 3: Red LED (
,
, Fig. 2)
(
(
Operating modes
Open-circuit sensor
or lead
Above or below limit
3
1
Caution! Observe note in Section 9.3
2
In relation to analogue output spans A1 and A2
3
Only applies when the output contact K is used for monitoring the
input variable in relation to a limit.
2
(see
∆ Measured variable
∆ t
2
/s (see
2
2
/s
Rate-of-change
of input variable
Slope
S
H
G
Time
Red LED
lit
lit / not lit
(acc. to programming)

Publicité

Table des Matières
loading

Table des Matières