SMA Solar Technology AG / SMA Solar Technology America LLC
9. The LCS tool prompts for a confirmation of the selected
country and grid code. See figure 5.7. A wrong
configuration can be changed by clicking the [Back]
button and by changing the settings in the previous
window.
Figure 5.7 LCS tool - checking the country and grid code
10. The system then applies the grid code selected on the
Inverter Manager to the detected inverters. Any
inverter added at a later stage automatically inherits
the same grid code. The application of only one grid
code is possible per Inverter Manager.
INFORMATION
It is essential to choose the correct grid code.
A modification after the first ten operating hours have
passed is only possible with a personal SMA Grid
Guard code.
The grid code parameters can be changed
subsequently with the LCS tool
(see section 5.2.6, page 24). Prerequisite is the use
of the latest version of the LCS tool.
11. A green square identifies the commissioned inverters.
The inverters are only connected to the utility grid when
the [Start] command has been carried out from the bar
below the start menu. See figure 5.8.
Installation Manual
5 LCS tool
IMVIOBOX-IA-xx-12
17