Digital Input - SMA INVERTER MANAGER Instructions D'installation

Masquer les pouces Voir aussi pour INVERTER MANAGER:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4 I/O Box
Diameter of the varistor leads
For safety reasons the varistor leads for the electricity
supply must have a diameter of at least 2 mm².
4.3.5 LED Signals of the I/O Box
LED
State
Power
Glowing
yellow
Off
Ready
Glowing
green
Green is
flashing once
per second
Flashing
green every
0.5 seconds
Flashing
green
Off
Port 1
Flashing
green
Port 2
Flashing
yellow
4.4 Technical Data
System data
Electricity supply
Cabling
Dimensions
Weight
Operating temperature
range
12
IMVIOBOX-IA-xx-12
Explanation
The I/O Box is in operation.
The I/O Box is not in operation.
The system is ready for
operation.
The "detect" function was
triggered.
Firmware is being updated.
When the green LED is on for
five seconds and then goes off
for five seconds, it means that
the system is in "Safe Mode".
The system is not ready for
operation.
Data is being sent or received.
Data is being sent or received.
24 Vdc nominal,
12 Vdc to 36 Vdc
I/O cable max. 4 AWG
27.8 mm x 124 mm x
84 mm (1.09 in x 4.88 in x
3.31 in)
< 200 g
Standard module:
-10°C to +75°C
14°F to 167°F
SMA Solar Technology AG / SMA Solar Technology America LLC
System data
Storage temperature
Relative humidity,
non-condensing
Operating altitude
Industry standards and
certifications

Digital input

Sensor type
I/O mode
Potential-free contact
Wet contact (DI to COM)
Insulation voltage
Counter/Frequency
-40°C to +85°C
-40°F to 185°F
5 % to 95 %
< 2000 m
UL 508, CE, FCC Class A
Potential-free contact
(NPN or PNP); wet contact
DI or event counter
On = ground fault
Off = open
On = 10 Vdc to 30 Vdc
Off = 0 Vdc to 3 Vdc
3000 Vdc or 2000 Veff
250 Hz, memory in off-state