Electrical Installation; Installation According To Emc Requirements - Lenze 8200 vector Instructions De Montage

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Show/Hide Bookmarks
Show/Hide Bookmarks
3

Electrical installation

Installation according to EMC requirements

A
Stop!
Control cables and mains cables must be separated from the motor cable to avoid interfe-
rences.
0
Function module (option)
1
Star or delta connection as indicated on the motor nameplate
2
EMC-cable connector (not included in the delivery package)
3
Shielded motor cable, low-capacity (core/core ≤ 75 pF/m; core/shield ≤ 150 pF/m)
4
Connect the cable screen to PE with a surface as large as possible (PES). Use enclosed clamps.
5
Control cable (optionally)
6
Mounting plate with electrically conductive surface
EMC
Compliance with EN 61800-3/A11
Noise emission
Noise emission
Compliance with limit value classes A and B to EN 55011
E82EVxxxKxB00x
E82EVxxxKxB20x
1)
Limit value class B: according to type
10
G
F
Abb. 1-8
without additional measures
only by means of external filters
EDK82EV3 DE/EN/FR 2.0
D
C
E
1)
B
M
3~
8200vec066
L

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Edk82ev3

Table des Matières