Media; Electrical Connections - Burkert MP05 Instructions De Service

Bloc multiple et profil pneumatique modulaire
Masquer les pouces Voir aussi pour MP05:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Media

• Filtered compressed air (max. particle size 10 µm), preferably non-oiled
• Operation is possible with oiled air
• Seal material:
• Perissible medium temperature:
• Perissible ambient temperature:
• Operational pressure range:
NOTE
The pilot pressure of the pneumatic controller is dependent on the pressure of the flow
of medium: it must not exceed a maximum of 8 bar!
ATTENTION!

Electrical connections

Pilot valve Type 6106
• Read the voltage, electrical power, type of protection and current from the rating plate!
• Voltage tolerance ±10 %;
• Ensure a long service life of the pilot valve by using a 10µ filter!
• Electrical connection: Instrument socket type 2506 to the tag connection on the coil (tigthening torque:
1 Nm);
• Proctection level IP 65 (only in combination with appliance socket type 2506);
• To match the cable run, the instrument socket can be mounted rotated by 180°.
NOTE
The coil heats up during opeation!
ATTENTION!
NBR
max. + 50 ° C
max. + 55 ° C
2 - 8 bar
Observe the permissible pressure range given on the rating plate!
Pressure difference between Ports 1 and 3 ³ 2 bar
For temperatures below 0 °C, operation is limited to dry-air operation.
Take note of the voltage used; with alternating current, always
use the instrument socket Type 2506, or connect a rectifier into the circuit!
When screwing down the instrument socket onto the coil, ensure that the flat
seal is well seated!
T
D
ECHNICAL
ESCRIPTION
5470 / MP05 - 9

Publicité

Table des Matières
loading