Parameter Overview; Error Codes - nVent RAYCHEM Raystat V5 Consignes D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 16

Parameter overview :

Operation
PARA-
Mode:
METER
PiPE
SP1
SP2
SP3
SP4
SP5
SP6
SP7
SP8
SP9
SP10
SP11
SP12
SP13

Error codes :

Error
Error
Code
description
Er 2.1 Sensor open
Er 2.2 Sensor short
High
Er 3.1
temperature
alarm
Low
Er 4.1
temperature
alarm
Er 6.x Internal error
Error codes will be displayed after a time delay of 10 min.
Operation
Mode:
Description
Air = PASC
SET
Temperature
Operation
mode
selection
Lowest
ambient
temperature
Average pipe
diameter level
Heater
operation in
sensor failure
mode
Heater
operation
via external
contactor
Hysteresis
Low
temperature
alarm
Higher
temperature
alarm
Alarm sound
status
TEST program
KEY LOCK –
Pass code
RESET
1. Check sensor cable connection
2. Verify operation of unit
3. Replace unit if cable ok & error still exists
1. Check sensor connection
2. Replace sensor
3. Replace unit if sensor ok & error still exists
1. Verify heating system and sensor position
2. Verify menu settings of high temperature alarm
1. Verify heating system and sensor position
2. Verify menu settings of low temperature alarm
Replace unit
Factory
settings
+3°C
-----
–20°C
2
>= DN 25 / 1"
ON
No
1 K
0°C
+65°C
ON
OFF
OFF
000
Remedy
nVent.com/RAYCHEM | 11
Parameters
0°C ... +90°C
PiPE / Air
–30°C ... 0°C
01 = Ø < DN
25 / 1"
02 = Ø ≥ DN
25 / 1"
03 = Ø ≥ DN
50 / 2"
ON/OFF
Yes/No
0 K ... 5 K
OFF/–40°C
OFF/+65°C
ON/OFF
ON/OFF
OFF/code
036
Code 012