  • Page 1 RAYSTAT-EX-02 Installation instructions Montageanleitung Instructions d’installation Instruções de instalação...
  • Page 3 ENGLISH 1 Cover over adjustment knob 3 3/4 inch NPT entry & dial 4 Capillary 2 Lid locking system 5 Bulb DEUTSCH 1 Abdeckkappe für 3 3/4 NPT-Innengewinde Einstellknopf 4 Kapillarrohr 2 Deckelfixierung 5 Sensor FRANÇAIS 1 Couvercle protégeant la 3 Entrée 3/4”...
  • Page 4 PORTUGUÊS 1 Tampa sobre botão de 3 Entrada NPT de 3/4 pol. ajuste e mostrador 4 Capilar 2 Sistema de travamento da 5 Bulbo tampa PORTUGUÊS Chave de fenda de 3 mm para Chaves de porca de 24 e 30 mm o terminal para GL-34 Chave de fenda Phillips...
  • Page 5 RAYSTAT-EX-02 ENGLISH Special conditions for Safe Use: According to IEC/EN 60079-1 regarding Installation instructions for nVent RAYCHEM thread maintenance applies: the RAYSTAT-EX-02. flamepaths are specified with maximum This thermostat is suitable for installation gaps smaller than those shown in the where the following are applicable: standard and shall not be enlarged.
  • Page 6 RAYSTAT-EX-02 DEUTSCH denen in der Norm vorgegebenen liegen müssen. Diese dürfen nicht Montageanleitung erweitert werden. Falls bei der Wartung Der Thermostat ist in folgenden erforderlich, sollte bezüglich der Anwendungen einsetzbar: Spaltweiten der Hersteller konsultiert In Heizkreisen mit Is 22 A werden.
  • Page 7 PORTUGUÊS aqueles indicados na norma e não devem ser aumentados. O fabricante deverá ser Instruções de instalação para RAYSTAT-EX-02. consultado para obtenção de valores, Este termostato é adequado para caso necessário para manutenção. instalação onde se aplica o seguinte: Especificação do circuito...
  • Page 8 ENGLISH DEUTSCH Enclosure installation Regler-Montage Alternative mounting Alternative arrangements are shown Montagemöglichkeiten siehe (4 mounting holes M6 oben (4 M6-Befestigungs- clearance on 101.5 x 101.5 mm bohrungen). centres). Zur exakten For optimised temperature Temperaturerfassung, Regler nicht in der Nähe des Sensors control locate enclosure remote from bulb.
  • Page 9 ENGLISH Maintenance Internal and external terminals Maintain thermostat during normal plant maintenance. are tight. CHECK: Thermostat operation correct. Mounting is firm. Thermostat set to suit Exposed capillary is not application. Dial cover closed firmly. damaged. Gland seal (grommet) is in Lid closed firmly.
  • Page 10 90° ENGLISH Bulb and capillary installation Location of bulb -  on lower quadrant of pipe 90° -  as indicated in the system design from single heating cable (B) documentation -  on lower quadrant of pipe -  away from heat sinks such as centrally between heating cables valves, flanges, supports or if two or more heating cables (C).
  • Page 11 Dimensions in mm ENGLISH Bulb and capillary installation WARNING: continued Do not bend bulb, keep it straight Attachment of bulb at all times. - fix bulb firmly on pipe surface with heating cable fixing tape in three places (D) - fix bulb parallel to pipe (D) - route capillary to avoid damage in use.
  • Page 12 3 Supply cable gland construction applicable. Failure 4 nVent RAYCHEM cable gland to remove any links between live 5 RAYSTAT-EX-02 terminals (terminal L above) in 6 Junction box...
  • Page 13 ENGLISH Cable connections continued 1 Ensure lid retaining grub screw is 7 Tighten lid retaining grub screw loose but is retained in plate 8 Where required connect external 2 Remove lid using spanner if earth terminal provided necessary WARNING: 3 Install cable through gland, fix Ensure lid retaining grub screw is gland in place firmly and terminate tightened fully to meet hazardous...
  • Page 14 ENGLISH Complete installation Ensure the pipe and bulb are When thermostat installation is thermally insulated and clad to complete test as described in the the design specification after Installation & Maintenance manual. installation of thermostat. Retain this instruction for Seal cladding with sealant at entry future use e.g.
  • Page 15 ENGLISH Setting Loosen fixing bolts and remove cover from dial. Adjust knob to required setting. Replace cover firmly by tightening fixing bolts. DEUTSCH Einstellung Abdeckkappe losschrauben. Regler auf gewünschte Schalt temperatur einstellen. Abdeckung wieder aufsetzen und fest verschrauben. FRANÇAIS Réglage Retirer les vis de fixation et déposer le couvercle du cadran.
  • Page 16 4 fixing holes (M6) on 101.5 x 101.5 mm centres Accessories Power cable gland for GL-33 493217-000 armoured cable Power cable gland for GL-34 931945-000 non-armoured cable (to be ordered separately) Ordering details Part description RAYSTAT-EX-02 PN (Weight) 404385-000 (1770 g) 16 | nVent.com...
  • Page 17 Rohrleitung oder Wandmontage (4 Montagelöcher (M6), Mittenabstand 101,5 x 101,5 mm) Zubehör (separat zu bestellen) Kabelverschraubung für GL-33 493217-000 armierte Zuleitungen Kabelverschraubung für GL-34 931945-000 nicht-armierte Zuleitungen Bestellinformationen Bestellbezeichnung RAYSTAT-EX-02 Bestellnummer & Gewicht 404385-000 (1,8 kg) nVent.com | 17...
  • Page 18 4 trous de fixation (M6) (101,5 x 101,5 mm) Accessoires de thermostat Presse-étoupe du câble GL-33 493217-000 d’alimentation armé Presse-étoupe du câble GL-34 931945-000 non armé (à commander séparément) Références de commande Désignation RAYSTAT-EX-02 PN & poids 404385-000 (1770 g) 18 | nVent.com...
  • Page 19 4 furos de fixação (M6) em centros de 101,5 x 101,5 mm Acessórios Prensa-cabo de alimentação GL-33 493217-000 para cabo blindado Prensa-cabo de alimentação GL-34 931945-000 para cabo sem blindagem (a ser pedido separadamente) Detalhes de pedido Descrição da peça RAYSTAT-EX-02 PN (peso) 404385-000 (1770 g) nVent.com | 19...