Sensor data
Approval
Sensor installation for higher temperature ranges:
For higher temperature ranges up to 250°C a PT100 type of sensor can be connected
by using the sensor-Plug-In Module SM-PT-100-1 (PCN: 1244-022441). A reset of
the unit is needed to recognize this new hardware module and to activate the new
temperature range.
Sensor
Temperature sensor
type
Sensor tip
dimensions
Sensor cable length
Cable extension
Temperature range
OPERATION
The Raystat V5 has a LED user screen interface: The unit will switch to the main
screen after 2 minutes of non-interaction on the parameter input screens.
Quick install
When the unit is powered up for the first time, a quick setup must be executed before
the unit is ready to start. The Quick start helps to set all important settings, the
unit will go in main screen mode automatically when done. Quick start is sufficient
for normal operations. More settings are available in the Setup menu for special
installation conditions.
The Quick start will only start if no pre-setting is done.
QUICK START
PARAMETER SETTING
10 | nVent.com/RAYCHEM
CE/UKCA mark; EMC According to EN 50081-
1/2 for emission and EN50082 - 1/2 for immu-
nity Temperature for ball pressure +100°C test
(DIN EN 60730/VDE 0631-1)
Rated impulse voltage: Overvoltage category III
(DIN EN 60730/ VDE 0631-1)
Standard
(included in box)
NTC 2 KOhm /
25°C, 2-wire
Ø 5 mm,
length 20 mm
5 m
Up to 150 m, min.
2 x 1,5 mm²
—40°C to +90°C
64
71
Temperature
–40°C
–35°C
–30°C
–25°C
–20°C
–15°C
–10°C
–5°C
0°C
+5°C
+10°C
+15°C
+20°C
+30°C
+40°C
+50°C
+60°C
+70°C
+80°C
With SM-PT100-1 Module
HARD-78
PT100
Ø 6 mm,
length 50 mm
3 m
Up to 150 m,
3 x 1,5 mm²
–40°C to +150°C
Resistance in kOhm
32,34
24,96
19,48
15,29
12,11
9,655
7,763
6,277
5,114
4,188
3,454
2,862
2,387
1,684
1,211
0,8854
0,6587
0,4975
0,3807
MONI-PT100-260/2
PT100
Ø 6 mm,
length 50 mm
2 m
Up to 150 m,
3 x 1,5 mm²
–50°C to +260°C