Installation and Operation Instructions
MiniVent M1/100/120
– For a simple assembly an exit is recommended as shown (turnable by 90° in each case).
– The optimal position is 45° each if the cable exit is directly at the position of the cable grommet.
– Duct inside diameter M1/100 = 100 mm or M1/120 = 120 mm
and distance to room corners: M1/100 at least 90 mm, M1/120 at least 110 mm.
– With regard to surface mounted cabling, the side entry knockout for the cable (Fig.9, Posâ) in the
casing must be broken out!
– The connection cable and the control line must be stored so that no water can get in along the cable
in case of water exposure. The cables must not be placed over sharp edges!
Fig�6
Cable exit
possible as
required in
dark area
min� 90 mm
min� 110 mm*
*
Type M1/120..
2� Drill holes:
Set casing against the wall, mark the holes and drill. Fasten with at least 2 screws and plugs.
3� Back draught shutter and guide van
– When installing the device, the guide vane must be mounted vertically (Fig.8).
Fig�7
Recommen-
ded cable
Cable routing under the casing� Cable
exit optional
length from wall at least
0���-360 °,
180 mm�
ideally 45°
drill holes
7