1.9 Low feed pressure Fault delay
Specify the length of time before the controller goes into Fault mode if low feed pressure condition
occurs (0...255 seconds). The pump will continue to run for this many seconds before Fault mode
is switched to. If set to 0, pump will stop running immediately after low feed pressure occurs. 1.10
High feed pressure switch
This setting specifies if high feed pressure switch is normally closed (NC) or normally open (NO)
type.
1.11 Permeate backpressure switch
This setting specifies whether backpressure switch is normally closed (NC) or normally open (NO)
type.
1.12 Backpressure Standby delay
Specify the length of time before the controller goes into Standby if high permeate pressure
condition occurs (0...255 seconds). Controller will continue to operate in Service mode for the set
length of time before running pre-Standby forward flush or will initiate Forward flush immediately
if value set to 0.
1.13 Tank level switch
This setting specifies whether float switch is normally closed (NC) or normally open (NO) type.
1.14 Tank level Standby delay
Specify the length of time before the controller goes into Standby if tank level switch goes high
(0...255 seconds). Controller will continue to operate in Service mode for the set length of time
before running pre-Standby forward flush or will initiate Forward flush immediately if value set to 0.
1.15 Display permeate TDS in ppm
If set to "on", electrical conductivity (EC) of permeate will be displayed as TDS in ppm as TDS =
0.5147 * EC.
1.16 Permeate conductivity Fault threshold
Specify maximum acceptable permeate conductivity. Conductivity reading above this value will
initiate Fault mode ('High permeate TDS'). If set to zero, fault threshold will not be used.
1.17 Permeate conductivity Fault delay
Specify the length of time before the controller goes into Fault mode when high permeate
conductivity is being read. Step 1.17 is displayed only if step 1.16 is set to non-zero value.
1.18 New settings and calibration passcode
Verify passcode.
This manual is the intellectual property of Ecosoft. Copying and reprinting is prohibited. © 2017
INSTRUCTION MANUAL ECOSOFT RO SYSTEM MINI (MO-6500, MO-12000, MO-24000)
23