The connection method of the rightward
outlet pipe.
S-shaped pipe
connection(Liqui
d side)
Liquid side
Elbow pipe
piping(field
connection
piping)
(Gas side)
The connection method of the downward
outlet pipe.
Liquid side piping
(field piping)
The recommended
length is about 400mm.
S-shaped pipe
connection(Liquid
side)
The connection method of the backward
outlet pipe.
S-shaped pipe
connection(Liquid
side)
Elbow pipe
connection
(Gas side)
Gas side piping
(field piping)
5.4.5 Connecting Branches
CAUTION
The wrong installation will cause the unit to
malfunction.
5.4.5.1 U-type branch joint
The branch joints should be as level as possible, and the
angular error does not exceed 10°.
U type branch joint
A-direction view
Error
Level
Gas side piping
(field piping)
Fig. 5.23
Gas side piping
(field piping)
The recommended
length is about 400mm.
S-shaped pipe
connection(Gas
side)
Fig. 5.24
The backward outlet
pipe should pass
through the gas-liquid
separator
Liquid side
piping(field
piping)
Fig. 5.25
A
Correct
10°
10°
Fig. 5.26
The branch joints come in different pipe diameters, which
can be easily matched with different pipe diameters.
When connecting pipes, select the pipe section with the
appropriate pipe diameter, cut it in the middle with a pipe
cutter and remove burrs, as shown in the figure below.
Middle of the pipe section
Use special pipe cutter
The length of the straight pipe section between the
continuous branch pipes shall be no less than 500mm.
The straight pipe section behind the branch pipe end
shall be no less than 500mm. The length of straight pipe
between two right angle bends shall be no less than
500mm.
≥500mm
≥500mm
≥500mm
≥500mm
Fig. 5.27
Fig. 5.28