INSTALLATIoN
Product description
2.3 Instructions, standards and regulations
Note
f observe all currently applicable regulations and
f
requirements.
3. Product description
The compact heat pump installation set WPKI-Set is a compo-
nent of the heat pump system and is specifically designed for
the hydraulic connection of the heat source and heat consumer
side. This connection is made via two brine/water heat pumps.
In addition to supplying the heating circuit with heating energy,
you can also use the heat pump system for domestic hot water
heating.
The WPKI-Set is delivered with components pre-assembled as
far as possible. It comprises pipework assemblies, circulation
pumps and non-return valves, as well as connections for the
heat source and heat consumer system.
Note
The following components are not part of the stan-
dard delivery:
- Brine circuit pump on the heat source side
- Circulation pump for DHW heating
Note
With brine | water heat pumps, the heat source can
also be used for cooling purposes, i.e. as a heat sink.
The HE circulation pump UP 30/7.5 E are suitable for
cooling operations.
3.1
Type of connection
Note
As of the 01/03/2012 (date of manufacture 8735) the
appliances WPF 10 M, WPF 13 M and WPF 16 M feature
an integral electrical connection for the brine circuit
pump as standard.
Two brine circuit pumps on the source side
Each heat pump is supplied by a separate brine circuit pump.
The brine circuit pumps are switched by the respectively
connected heat pump.
12 |
9
8
3
4
7
1 Heating flow
2 Heat source flow
3 Circulation pump for charging the buffer cylinder
4 Brine circuit pumps, source side
5 optional DHW return
6 optional DHW flow
7 Assembly including safety valve, pressure gauge and air
vent valve
8 Heat source return
9 Heating return
3.2 Standard delivery
The following are delivered with the appliance:
- 2 HE circulation pumps UP 30/7.5E
- 2 non-return valves G2
- 1 pipework assembly
- 10 gaskets 56 x 42 x 2
- 10 gaskets 38.8 x 27.0 x 4.0
- 1 heat pump manager WPM
- 2 adaptors G 1¼ - G 2
- 2 inserts G 2 - 28
- 2 union nuts G 2
3.3 Accessories
3.3.1 Required accessories
Source pumps:
- 2 brine circuit pumps UP 30/1-8E
or
- Brine assembly
3.3.2 Further accessories
- Flexible pipes as anti-vibration fittings, thermally insulated
G 2 x 1 m (DN50); G 1¼ x 1 m (DN32)
- Circulation pump UP 25/7.5 PCV for DHW heating