5 RÉGLAGES
CHEMIN: RÉGLAGES
ÉLÉMENTS DE CDE
RÉ-ENCLENCHEMENT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
RÉ-ENCLENCHEMENT
FNCTION RE-ENCLCHMT:
Déactivé
MODE RÉ-ENCLECHMENT:
Mon_tripol
RE NOMBRE MAX DE
MANVRS: 2
RE VERROUILLGE DSJ1:
Hrs
RE TEMPS FERM DSJ1:
0.10 s
RE FERM MNUELLE DSJ:
Hrs
RE TEMPS VER SUR FRM
MANL:
10.00 s
RE MONOPOL INITIATN:
Hrs
RE TRI-POL INITIATN:
Hrs
RE TMPO TRIPOL INIT:
Hrs
RE DÉFAUT MULTIPHSE:
Hrs
DISJ UNE PHASE OUVT:
Hrs
DISJ 3 PHSES OUVERT:
Hrs
RE TMPS MORT1 3-POL:
0.50 s
RE TMPS MORT2 3-POL:
1.20 s
RE TMPS MORT3 3-POL:
2.00 s
RE TMPS MORT4 3-POL:
4.00 s
RE EXT TEMPS MORT1:
Hrs
RE EXTENSION TEMPS
MORT 1: 0.50 s
RE RAPPEL:
Hrs
RE TEMPS RAPPEL:
60.00 s
Relais de courant différentiel de ligne L90
5.6 ÉLÉMENTS DE CONTRÔLE
5.6.10 AUTO RÉ-ENCLENCHEMENT
Portée: Déactivé, Activé
Portée: Mon_tripol, Monopl, Tripol-A, Tripol-B
Portée: 1, 2, 3, 4
MC
Portée: opérande FlexLogic
Portée: 0.00 à 655.35 s en étapes de 0.01
MC
Portée: opérande FlexLogic
Portée: 0.00 à 655.35 s en étapes de 0.01
MC
Portée: opérande FlexLogic
MC
Portée: opérande FlexLogic
MC
Portée: opérande FlexLogic
MC
Portée: opérande FlexLogic
MC
Portée: opérande FlexLogic
MC
Portée: opérande FlexLogic
Portée: 0.00 à 655.35 s en étapes de 0.01
Portée: 0.00 à 655.35 s en étapes de 0.01
Portée: 0.00 à 655.35 s en étapes de 0.01
Portée: 0.00 à 655.35 s en étapes de 0.01
MC
Portée: opérande FlexLogic
Portée: 0.00 à 655.35 s en étapes de 0.01
MC
Portée: opérande FlexLogic
Portée: 0 à 655.35 s en étapes de 0.01
5
5-249