5.2 MONTAGE DU PRODUIT
Des modifications au réglage de
redémarré.
NOTE
e) PROTOCOLE DNP
CHEMIN: RÉGLAGES
PROTOCOLE DNP
5
5-16
NUMÉRO DE PORT TCP MODBUS
RÉGLS CONFIGURATN DU PRODUIT
CANAUX DNP
ADRESSE DNP:
MESSAGE
255
ADRESSES CLIENT
MESSAGE
RÉSEAU DNP
NUMÉRO PORT TCP/UDP
MESSAGE
DNP: 20000
FNCTN DNP RPNSE NON
MESSAGE
SOLLICITÉ: Déactivé
TPS ÉCOULÉ DNP
MESSAGE
RÉPNS NS: 5 s
TENTATIVES MAX DNP
MESSAGE
RÉP NON SOL: 10
ADRESSE DSTNTION DNP
MESSAGE
RÉP NON SOL: 1
FACTEUR DNP ÉCHELLE
MESSAGE
COURANT: 1
FACTEUR DNP ÉCHELLE
MESSAGE
TENSION: 1
ÉCHELLE DNP PSSANCE
MESSAGE
FCTEUR: 1
ÉCHELLE DNP ÉNERGIE
MESSAGE
FCTEUR: 1
DNP FACTEUR D'ÉCHELLE
MESSAGE
FP: 1
ÉCHELLE DNP AUTRE
MESSAGE
FCTEUR: 1
BANDE MORTE CRNT DNP
MESSAGE
PAR DFAUT: 30000
BANDE MORTE TNSN DNP
MESSAGE
PAR DFAUT: 30000
BANDE MORTE PSNC DNP
MESSAGE
PAR DFAUT: 30000
BANDE MORTE ÉNRG DNP
MESSAGE
PAR DFAUT: 30000
DNP BANDE MORTE FP
MESSAGE
PAR DÉFAUT: 30000
BANDE MORTE AUTR DNP
MESSAGE
PAR DÉFAUT: 30000
Relais de courant différentiel de ligne L90
ne prendront pas effet jusqu'à ce que le L90 soit
COMMUNICATIONS
PROTOCOLE DNP
Portée: présenté ci-dessous
Portée: 0 à 65519 en étapes de 1
Portée: Presser la clé MESSAGE
ADRESSES CLIENT RÉSEAU DNP
Portée: 1 à 65535 en étapes de 1
Portée: Déactivé, Activé
Portée: 0 à 60 s en étapes de 1
Portée: 1 à 255 en étapes de 1
Portée: 0 à 65519 en étapes de 1
Portée: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Portée: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Portée: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Portée: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Portée: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Portée: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Portée: 0 à 100000000 en étapes de 1
Portée: 0 à 100000000 en étapes de 1
Portée: 0 à 100000000 en étapes de 1
Portée: 0 à 100000000 en étapes de 1
Portée: 0 à 100000000 en étapes de 1
Portée: 0 à 100000000 en étapes de 1
5 RÉGLAGES
pour entrer le
GE Multilin