Designation
Color
DIAG
Green
Red
Red
BF
Red
Red
-
SF
Red
Red
-
L/A 1
Green
L/A 2
Yellow
-
11.3 Pin assignment
Table 6: Pin assignment X7E1/X7E2
Pin
Meaning
1
TD+
2
RD+
1
2
3
TD-
4
3
4
RD-
Housing
Ground
Table 7: Pin assignment power supply
Pin
Meaning
1
24 V DC power supply of the sensors/electronics (UL)
2
24 V DC actuator voltage (UA)
2
1
3
0 V DC power supply of the sensors/electronics (UL)
3
4
4
0 V DC actuator voltage (UA)
12 Disposal
Improper disposal will lead to pollution of the environment. Furthermore, the
materials can no longer be recycled.
Dispose of the product, the packaging and any escaping operating materials
u
in accordance with the applicable national regulations.
13 Troubleshooting
13.1 Procedure
Step 1: Check the system
In case of malfunctions, first check the system or the system part where the
u
product is installed. Check the following items:
• All connections. See g 9. Service.
• Settings. See
g 14. Technical
Step 2: Check the product
1. Make sure the system or system part is not under pressure or voltage.
2. Check the product based on the fault patterns described below.
3. Perform troubleshooting using the information under "Remedy".
If the malfunction cannot be eliminated as described under "Remedy": Disas-
semble the product and return it. See
4. After the malfunction has been eliminated; Put the system or product back
into operation.
AVENTICS™ PROFINET-IO | 570088-BAL-AA | English
State
Meaning
Illuminates
State of the hardware is ok
Flashes (1 Hz)
Diagnostic message of the product
available
Illuminates
Hardware error of the valve system
Flashes (1 Hz)
Connection to master interrupted
Illuminates
No configuration
No physical connection
Slow physical connection
Off
The product exchanges data cycli-
cally with the control.
Flashes (1 Hz)
DCP signal service initiated via the
bus.
Illuminates
Watchdog timeout
Channel diagnosis, general diagno-
sis or extended diagnosis available.
System error
Off
No error
Illuminates
Physical connection to network de-
tected.
Flashes
Receive data package.
Off
No physical connection to network
detected.
data.
g 4.3 Returning the
product.
13.2 Malfunction types
Error
Possible cause
No output pressure at the
• No power supply con-
valves
nected to the product.
See LED display
• No supply pressure avail-
able.
Output pressure too low
Supply pressure too low.
Power supply for the product
not sufficient.
Air is audibly escaping
Leakage between product
and supply.
Pneumatics incorrectly con-
nected.
Name was not deleted when
A save operation was trig-
setting the address 0x00
gered before the address
0x00 was set
LED UL/UA flashes green
The supply voltage is less
than the lower tolerance limit
(18 V DC) and more than
10 V DC
LED UL/UA illuminates red
The valve supply voltage is
less than 21.6 V DC
LED UL/UA is off
The supply voltage is less
than 10 V DC
LED UL/UA flashes red
The supply voltage is greater
than 26.4 V DC
LED DIAG flashes red
No module connected to the
product
Diagnostic message for open
load/short circuit at valve
available.
LED DIAG illuminates red
Diagnostic message available. Check module.
Internal connection error or
hardware error.
Product is not detected.
LED BF illuminates red
Serious network error
LED BF flashes red
Connection to master has
been disconnected. No com-
munication via PROFINET IO
possible.
Error in the PLC configuration. Check PLC configuration.
LED L/A 1 or LED L/A 2 illumi-
No data exchange with the
nates green and flashes yel-
bus coupler.
low
Bus coupler has not been con-
figured in the control.
LED L/A 1 or LED L/A 2 is off
No connection to network
participant.
Connecting cable damaged.
Network participant dam-
aged.
Product damaged.
14 Technical data
This section contains an excerpt of the most important technical data. Further
technical data can be found on the product page in the Emerson store.
Remedy
Apply power supply on plug
connector X1S.
Check power supply polarity.
Switch on system compo-
nent.
Connect supply pressure.
Increase supply pressure.
Check LED on the product.
Apply sufficient power sup-
ply.
Check the supply connection.
Check the pneumatic connec-
tion.
1. Separate power supply
2. Set the address between
1 and 254 (0x01and
0xFE).
3. Establish the power sup-
ply.
4. Wait 5 s, then separate
power supply.
5. Set address switch to
0x00.
6. Establish the power sup-
ply.
Check power supply on plug
connector X1S.
Connect the module.
Check the connection of the
valves.
Contact manufacturer
Check network settings
Check the connection to the
master.
Connect network section with
the control.
Bus coupler configured in the
control.
Connect fieldbus connection
X7E1 or X7E2 to network par-
ticipant.
Replace connecting cable.
Replace network participant.
Replace product.
20