Code table
Code
No.
Name
C0121
Activation class
1 Motor 1
2 Motor 2
C0122
C0122
Motor phase
Motor phase
f il
failure message
C0123
C0123
Message:
Message:
2
2
I
I
t
t-overload
l d
C0135
starttec control
word
(parameter
(parameter
channel)
96
Possible settings
Lenze
Selection
2
Activation class 10
2
Activation class 10
2
0
I
t-monitoring switched off
1
Activation class 10A
2
Activation class 10
3
Activation class 20
4
Activation class 30
0
0
0
TRIP
1
Warning
0
0
0
TRIP
1
Warning
starttec control via parameter channel. The
most important control commans are
grouped as bit commands.
Bit
Assignment
0
Motor 1 start/stop
0 Motor 1 start
1 Motor 1 stop
1
Motor 2 start/stop or selection of
direction of rotation
0 Motor 2 start or CW rotation
1 Motor 2 stop or CCW rotation
2
Brake control
0 Brake activation
1 Brake release
3
...
Reserved
Reserved
8
9
starttec enable/inhibit
0 starttec inhibit
1 starttec enable
10
TRIP set
0 No fault
1 External error active
11
TRIP reset
0 Þ 1 Transition resets error
12
...
Reserved
Reserved
15
EDK71MMXXX-010 DE/EN/FR 2.0
IMPORTANT
Activation characteristic,
Activation characteristic,
see ^ 69
^ 69
Change only active after the
Change only active after the
starttec is enabled again
t tt
i
bl d
i
C0135 cannot be changed
using the hand terminal
E E E E E E E E r r r r
E E E E E E E E r r r r
Sets "external error" (
Sets external error (
LECOM No. 91)
Reason for error must be
easo o e o
ust be
eliminated