  • Page 1 Show/Hide Bookmarks EDK71MMXXX-010 !NBY Montageanleitung Mounting Instructions Instructions de montage starttec Motorstarter Typ 1 Type 1 motor starter Démarreur moteur type 1...
  • Page 2 Show/Hide Bookmarks ã 2002 Lenze Drive Systems GmbH 2.0 04/2002 TD00...
  • Page 3 Show/Hide Bookmarks Erst Montageanleitung lesen, dann mit den Arbeiten beginnen! Beachten Sie die enthaltenen Sicherheitshinweise. Read the Mounting Instructions before you start working! Please observe all safety information given. Lire attentivement les instructions de montage avant toute opération ! Respecter les consignes de sécurité. start209...
  • Page 4 Show/Hide Bookmarks Diese Dokumentation ist gültig für den Motorstarter starttec ab dem Gerätestand E71MM402 AS-interface _ = nicht aktiv F = aktiv DC-Spannung Federkraftbremse 2 = 205 VDC 4 = 180 VDC Ausführung x1x = Einzelantrieb x2x = Mehrmotorenbetrieb, Drehrichtungswechsel Hardwarestand Softwarestand Legende zur Abbildung...
  • Page 5 Show/Hide Bookmarks Schnelle Inbetriebnahme Sicherheitshinweise lesen ^ 17 starttec montieren Mindestverdrahtung herstellen 3/N/PE AC 100 … 550 V 45 … 65 Hz +24 V DC (+18 VDC - 0 % … +30 VDC + 0 %, 200 mA ... 1.5 A) ^ 20 L1 L2 L3 20 28...
  • Page 6: Table Des Matières

    ..........Lenze Niederspannungsmaschinen .
  • Page 7: Sicherheitshinweise

    Lenze-Motorstarter-1- (gemäß Niederspannungsrichtlinie 73/23/EWG) 1. Allgemein Lenze-Motorstarter können während des Betriebs - ihrer Schutzart entsprechend - spannungsführende, auch bewegliche oder rotierende Teile haben. Oberflächen können heiß sein. Bei unzulässigem Entfernen der erforderlichen Abdeckung, bei unsachgemäßem Einsatz, bei falscher Installation oder Bedienung besteht die Gefahr von schweren Personen- oder Sachschäden.
  • Page 8 Show/Hide Bookmarks Sicherheitshinweise Motorstarter 5. Elektrischer Anschluß Beachten Sie bei Arbeiten an unter Spannung stehenden Motorstartern die geltenden nationalen Unfallverhütungsvorschriften (z. B. VBG 4). Führen Sie die elektrische Installation nach den einschlägigen Vorschriften durch (z. B. Leitungsquerschnitte, Absicherungen, Schutzleiteranbindung). Zusätzliche Hinweise enthält die Dokumentation. Die Dokumentation enthält Hinweise für die EMV-gerechte Installation (Schirmung, Erdung, Anordnung von Filtern und Verlegung der Leitungen).
  • Page 9: Lenze Niederspannungsmaschinen

    Show/Hide Bookmarks Sicherheitshinweise Lenze Niederspannungsmaschinen Allgemeine Sicherheits - und Anwendungshinweise für Lenze-Niederspannungsmaschinen (gemäß Niederspannungsrichtlinie 73/23/EWG) 1. Allgemein Niederspannungsmaschinen haben gefährliche, spannungsführende und rotierende Teile sowie möglicherweise heiße Oberflächen. Alle Arbeiten zu Transport, Anschluß, Inbetriebnahme und Instandhaltung sind von qualifiziertem, verantwortlichem Fachpersonal auszuführen (EN 50110-1 (VDE 0105-100); IEC 60364 beachten). Unsachgemäßes Verhalten kann schwere Personen- und Sachschäden verursachen.
  • Page 10 Show/Hide Bookmarks Sicherheitshinweise Lenze Niederspannungsmaschinen 5. Elektrischer Anschluß Alle Arbeiten dürfen nur von qualifiziertem Fachpersonal an der stillstehenden Niederspannungsmaschine im freigeschalteten und gegen Wiedereinschalten gesicherten Zustand vorgenommen werden. Das gilt auch für Hilfsstromkreise (z. B. Bremse, Geber, Fremdlüfter). Spannungsfreiheit prüfen! Überschreiten der Toleranzen in EN 60034-1;...
  • Page 11: Restgefahren, Gestaltung Der Sicherheitshinweise

    Show/Hide Bookmarks Sicherheitshinweise Restgefahren, Gestaltung der Sicherheitshinweise Restgefahren Personenschutz Alle Leistungsanschlüsse (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 und BN) können lebensgefährliche elektrische Spannung führen, wenn der starttec an das Netz ge- schaltet ist. Schalten Sie deshalb den starttec spannungslos, bevor Sie Arbeiten daran durchführen oder das Gehäuse öffnen.
  • Page 12 Show/Hide Bookmarks Sicherheitshinweise Restgefahren, Gestaltung der Sicherheitshinweise Gestaltung der Sicherheitshinweise Alle Sicherheitshinweise in dieser Anleitung sind einheitlich aufgebaut: Piktogramm (kennzeichnet die Art der Gefahr) Signalwort (kennzeichnet die Schwere der Gefahr) Hinweistext (beschreibt die Gefahr und gibt Hinweise, wie sie vermieden werden kann) Signalwort Piktogramm...
  • Page 13: Technische Daten

    Show/Hide Bookmarks Technische Daten Allgemeine Daten Konformität Niederspannungsrichtlinie (73/23/EWG) EMV-Richtlinie (93/68/EWG) Approbationen UL 508 Underwriter Laboratories (File-No. E132659) Power Conversion Equipment (in Vorbereitung) Normen DIN EN 60947-4-2 Halbleiter-Motor-Steuergeräte und -Starter für Wechsel- spannung Rüttelfestigkeit Beschleunigungsfest bis 4g (Germanischer Lloyd, allgemeine Bedingungen) Klimatische Bedingungen Klasse 3K3 nach EN 50178 (ohne Betauung, mittlere relative Feuchte 85 %) Verschmutzungsgrad...
  • Page 14: Bemessungsdaten

    (geschaltete Spannung) Max. Ausgangs-Dauerstrom 9.5 A (Summe der Ausgangsströme) zyklisches Schalten max. 1 Schaltung / s Motorleistung (Lenze-Motoren) an 3/PE AC 230 V P 0.25 ... 2.2 kW an 3(/N)/PE AC 400 V P 0.25 ... 4.0 kW max. 9.5 A max.
  • Page 15 0.01 0.02 1000 10000 t [s] start031 Class 10A Class 10 = Lenze-Einstellung Auslöseklassen einstellbar in C0121 Auslöseklassen, einstellbar in C0121 Class 20 Class 30 Ausgangsstrom Motor-Bemessungsstrom, einstellbar in C0120 oder mit Stufenschalter Beispiel für Der starttec schaltet mit einer Fehlermeldung ab, wenn der Ausgangsstrom I ca. 13 s lang...
  • Page 16: Abmessungen, Mechanische Ausführung

    Show/Hide Bookmarks Technische Daten Abmessungen, Mechanische Ausführung Abmessungen start001 a [mm] b [mm] c [mm] d [mm] e [mm] 228.0 10.0 104.5 129.0 71.0 Mechanische Ausführung Gehäuse Verschraubungen Gewicht Gehäuse mit Elektronikmodul aus 4 × M20 (Gewindelänge 10 mm) Aluminium-Druckguß 6 ×...
  • Page 17: Lieferumfang

    Show/Hide Bookmarks Lieferumfang -5-start010 Gehäuse mit Elektronikmodul Gehäusedeckel Distanz- und Wandplatte Dichtung Schrauben KA 50 × 18 EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 18: Mechanische Installation

    Show/Hide Bookmarks Mechanische Installation Motormontage 3.4 Nm 30 lb-in 68-73mm 4 × 6 × start024 Schraube (DIN 7985) 20 mm, max. M5 Fächerscheibe nach DIN 6798 EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 19: Wandmontage

    Show/Hide Bookmarks Mechanische Installation Wandmontage 5.3 mm 4 × 6 × 3.4 Nm 30 lb-in start022 Distanz- und Wandplatte Bohrbild Abstand a [mm] b [mm] c [mm] d [mm] e [mm] EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 20: Elektrische Installation

    Show/Hide Bookmarks Elektrische Installation Wichtige Hinweise Gefahr!-6- Alle Leistungsanschlüsse (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 und BN) können lebensgefährliche elektrische Spannung führen, wenn der starttec an das Netz geschaltet ist. Schalten Sie deshalb den starttec spannungslos, bevor Sie Arbeiten daran durchführen oder das Gehäuse öffnen.
  • Page 21: Anschlußplan

    Anschluß Netz max. 4 mm (AWG 10) 1U, 1V, 1W Anschluß Motor 1 ^ 23 B1, B2, BN Anschluß Lenze-Federkraftbremse BFK457 oder BFK458 X3/59 Anschluß Versorgungsspannung +24 VDC +18 VDC - 0 % ... +30 VDC + 0 %) Bezug: X3/7 min.
  • Page 22 Show/Hide Bookmarks Elektrische Installation Anschlußplan Klemme Funktion (fett = Lenze-Einstellung) Daten Digitale Eingänge X3/28 X3/28 starttec freigeben/sper- starttec freigeben/sper LOW (0 V ... +3 V) LOW (0 V ... +3 V) HIGH starttec freigegeben HIGH (+12 V ... +30 V) LOW starttec gesperrt = >...
  • Page 23: Anschluß Federkraftbremse

    Show/Hide Bookmarks Elektrische Installation Anschluß Federkraftbremse Gefahr!-7- Alle Leistungsanschlüsse (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 und BN) können lebensgefährliche elektrische Spannung führen, wenn der starttec an das Netz geschaltet ist. Schalten Sie deshalb den starttec spannungslos, bevor Sie Arbeiten daran durchführen oder das Gehäuse öffnen.
  • Page 24 Show/Hide Bookmarks Elektrische Installation Anschluß Federkraftbremse Anschlußplan starttec E71MM402x2Axxx (Motor in * * * * -Schaltung, BN-Leiter vom Motor-Sternpunkt) Netz 3/PE AC 400 ... 500 V, Bremsenspannung 205 ... 257 VDC Nullpotential am Sternpunkt liegt erst ab einer bestimmten Motorspannung an. Erst dann steht die Bremsenspannung zur Verfügung.
  • Page 25: Anschluß As-Interface

    Show/Hide Bookmarks Elektrische Installation Anschluß AS-interface Hinweis! Das AS-interface ist nur aktiv bei starttec Typ E71MM402FxAxxx!-8- Kommunikationsdaten Protokoll / Kommunikationsmedium AS-i Netzwerk-Topologie Baum Busteilnehmer Slave Slave-Profil S-7.F (IO-Code: 7 , ID-Code: F Betriebsparameter Datenstruktur 3 AS-i Datenbit (D0, D1, D2) zum starttec 2 AS-i Datenbit (D0, D1) vom starttec max.
  • Page 26: Konfiguration

    Show/Hide Bookmarks Elektrische Installation Anschluß AS-interface Konfiguration Datenbits zum starttec: In C0410 (Auswahl 6, 7, 8) können Sie die Datenbits D0, D1 und D2 internen Digitalsignalen zuordnen. Datenbits vom starttec: In C0415, Subcode 5 und 6 können Sie den Datenbits D0 und D1 interne Digitalsignale zuordnen. Beispiel: Über AS-i soll der starttec freigegeben und dann ein Bremsmotor gestartet werden.
  • Page 27: Anschluß Bus-Funktionsmodule

    Show/Hide Bookmarks Elektrische Installation Anschluß Bus-Funktionsmodule Sie können den starttec über die Schnittstelle FIF an folgenden Bus-Systemen betreiben: Bus-System benötigtes Lenze-FIF-Modul PROFIBUS-DP E82ZAFP 001 INTERBUS E82ZAFI 001 Systembus (CAN) E82ZAFC 001 DeviceNet/CANopen E82ZAFD 001 LECOM-B (RS485) E82ZAFL 001 Hinweis! Für die Montage eines FIF-Moduls benötigen Sie den Montagesatz E71ZJ001! –...
  • Page 28: Wichtige Betriebsparameter Einstellen

    5.5 kW Einstellung Bemerkung Stellen Sie mit dem Stufenschalter siehe auch ^ 15 den Motor-Bemessungsstrom ein Mit dem Handterminal Lenze-Einstellung: 1 = 1.0 A können Sie in C0120 die Einstellung überprüfen oder ändern 3.0 A start032 Stellen Sie die Hochlaufzeit t Mit dem Handterminal kön-...
  • Page 29: Inbetriebnahme

    Show/Hide Bookmarks Inbetriebnahme Vor dem ersten Einschalten Stop!-10- Kurzschlüsse oder Erdschlüsse in der Verdrahtung zerstören den starttec. Überprüfen Sie die Verdrahtung auf Kurzschluß und Erdschluß. Um Personenschäden oder Sachschäden zu vermeiden, überprüfen Sie die Verdrahtung auf Vollständigkeit, Kurzschluß und Erdschluß. die Funktion ”NOT-AUS”...
  • Page 30: Ohne Handterminal

    Show/Hide Bookmarks Inbetriebnahme Ohne Handterminal Hinweis! Halten Sie die Einschaltreihenfolge ein. Bei Störungen während der Inbetriebnahme hilft Ihnen das Kapitel ”Störungen erkennen und beseitigen”. Einschaltreihenfolge Bemerkung Sicherstellen, daß nach Netz-Ein- Klemme X3/28 = LOW schalten der starttec gesperrt ist Netz einschalten 24 VDC-Versorgung einschalten starttec freigeben Klemme X3/28 = HIGH...
  • Page 31: Mit Handterminal

    Show/Hide Bookmarks Inbetriebnahme Mit Handterminal Das Handterminal E82ZBB und die notwendige Verbindungsleitung sind als Zubehör erhältlich. Die vollständige Beschreibung finden Sie im Faltblatt, das dem Handterminal beiliegt. Funktionstasten Statusanzeigen Bargraph-Anzeige Funktionsleiste 1 Funktionsleiste 2 Parametersatz Änderung Änderung Codenummer möglich, möglich, wenn Anzeige Subcodenummer blinkt...
  • Page 32 Show/Hide Bookmarks Inbetriebnahme Mit Handterminal Wechsel zwischenden Menüs u u u u S S S S E E E E r r r r und A A A A L L L L L L L L -12- uSEr Œ j g f k i h PS 0517 ‚...
  • Page 33 Betriebs an die Schnittstelle AIF anschließen, stehen sofort die 10 Codes zur Verfügung, die im Menü user (Code C0517) festgelegt wurden. Werkseitig enthält das Menü user alle Codes, um eine Standardanwendung in Betrieb zu nehmen: Code Bezeichnung Lenze-Einstellung C0054 Motor-Scheinstrom Motor 1 Nur Anzeige C0055 Motor-Scheinstrom Motor 2 Nur Anzeige...
  • Page 34 Show/Hide Bookmarks Inbetriebnahme Mit Handterminal Parameter in den Menüs ändern Schritt Tasten- Display Bemerkung Beispiel folge starttec Nur notwendig, wenn Sie Codes ändern wol- len, die in der Codetabelle mit s gekenn- sperren zeichnet sind, z. B.: C0002 Alle anderen Parameter können Sie während des Betriebs ändern.
  • Page 35 Handterminal zu ändern, PT: Potentiometer ”T” für PT: Potentiometer ”T” für C0006 entsprechend einstellen C0006 e tsp ec e d e ste e Hochlaufzeit Hochlaufzeit Lenze-Einstellung: -0- S: Stufenschalter für Mo- tor-Bemessungsstrom H: Handterminal H: Handterminal Wichtig! Wichtig! Bei der Umschaltung auf...
  • Page 36 Verknüpfung externer Si-  j g f k i h PS 04 10 gnalquellen mit internen Di- 00 1 gitalsignalen Lenze-Einstellung: Weitere Einstellmöglichkei- C0410/1 = 1: ten siehe Codetabelle start039 – X3/E1: Motor 1 Start/Stopp ( ^ 38) C0410/2 = 2: –...
  • Page 37 Verlauf der Spannung an Boff 1U, 1V, 1W (Motor 1)          Lenze-Einstellung: 0.00 s Ansteuerung der Bremse an B1, B2 start014 start014 Verlauf der Bremsspan- nung an B1, B2 CINH CINH CINH CINH CINH...
  • Page 38: Codetabelle

    S S S S E E E E r r r r ist nach jedem Netzeinschalten aktiv. Bezeichnung Bezeichnung des Code Lenze Lenze-Einstellung (Wert bei Auslieferung oder nach Wiederherstellen des Lieferzustands mit C0002) Die Spalte ”WICHTIG” enthält weitere Information à Auswahl 99 min.
  • Page 39 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0002 Parametersätze Mit dem Handterminal kön- mit Handtermi- nen Sie die Parameter zu nal übertragen nal übertragen anderen starttec übertragen u u u u S S S S E E E E r r r r u u u u S S S S E E E E r r r r ð...
  • Page 40 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0005 Feste Konfigu- Alle digitalen Eingangssignale kom- ration Ein- ration Ein men von der Klemmenleiste X3 gangssignale Alle digitalen Eingangssignale kom- Setzt C0410/x = 200 men vom Feldbus-Funktionsmodul auf FIF (z. B. INTERBUS oder...
  • Page 41 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl Der starttec erkennt, ob C0014 Betriebsart Betrieb mit einem Motor oder die Verdrahtung für Mehrmotorenbetrieb Mehrmotorenbetrieb oder für Drehrichtungsumkehr durchgeführt ist. C0014 wird automatisch ange- wird automatisch ange- Drehrichtungsumkehr oder Betrieb paßt!
  • Page 42 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0120 Motor-Bemes- {0.1 A} 9.5 Siehe Typenschild des Mo- sungsstrom tors u u u u S S S S E E E E r r r r Übernimmt den Wert des 1 Motor 1 à...
  • Page 43 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0135 starttec-Steuer- Steuerung des starttec über Parameterka- C0135 ist mit dem Handter- wort (Parame- nal. Die wichtigsten Steuerbefehle sind in minal nicht veränderbar terkanal) terkanal) Bitbefehlen zusammengefaßt Belegung Motor 1 Start/Stopp...
  • Page 44 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0150 starttec-Status- Abfrage des Status über Parameterkanal. Einige Bit sind in C0417 wort 1 (Para- Die wichtigsten Statusinformationen sind als frei mit internen Digital- meterkanal) Bitmuster zusammengefaßt signalen verknüpfbar Im Handterminal: Nur...
  • Page 45 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl Veränderungen nur durch C0165 Service-Code Lenze-Service! LECOM C0170 Konfiguration TRIP-Reset über Bus- TRIP-Reset durch Schalten der TRIP-Reset Funktionsmodul mit 24 VDC-Versorgungsspannung, C0043, C0410/12 oder LOW–Flanke an X3/28, Bus-Funk- C0135 Bit 11...
  • Page 46 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0352 Konfiguration Änderung wird nach Befehl Slave Systembus-Teil- Systembus-Teil- ”Reset-Node” wirksam ”Reset-Node” wirksam Master nehmer C0353 Quelle System- Quelle der Adresse für Sy- bus-Adresse stembus Prozeßdatenka- näle 1 CAN1 (Sync)
  • Page 47 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0356 Systembus Zeiteinstellun- 3000 0 {1 ms} 65000 Notwendig für CAN-Verbund 1 boot up ohne Master 2 Zykluszeit 0 und C0360 = 0: ereignis- CAN-OUT2 gesteuerte Prozeßdaten- übergabe > 0 und C0360 = 1: zykli- sche Prozeßdatenübergabe...
  • Page 48 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0372 C0372 Identifizierung Identifizierung Nur Anzeige Nur Anzeige kein Funktionsmodul F kti Funktionsmodul Systembus (CAN) anderes Bus-Funktionsmodul auf FIF, z. B. INTERBUS, PROFIBUS-DP, keine gültige Erkennung 20.00 Das mit X3/Ex verknüpfte C0408 Mindest-Ein- 0.00...
  • Page 49 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0410 Konfiguration digitale Ein- Verknüpfung externer Signalquellen gangssignale u u u u S S S S E E E E r r r r mit internen Digitalsignalen 1 Motor 1 Start/...
  • Page 50 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0410 C0410 Externe Signalquellen Nicht belegt u u u u S S S S E E E E r r r r S S S S E E E E...
  • Page 51 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0415 Konfiguration digitale Aus- Ausgabe interner Digitalsignale auf gangssignale u u u u S S S S E E E E r r r r Klemmen oder AS-interface 1 Digitaler Aus-...
  • Page 52 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl C0415 Scheinstrom (C0054) < Strom- Keilriemenüberwachung schwelle (C0156/1) Motor 1 u u u u S S S S E E E E r r r r Scheinstrom (C0055) < Strom- Keilriemenüberwachung...
  • Page 53 Show/Hide Bookmarks Inbetriebnahme Codetabelle Code Einstellmöglichkeiten WICHTIG Bezeichnung Lenze Auswahl Die Zuordnung wird abge- C0417 Konfiguration bildet auf das starttec-Status- Ausgabe interner Digitalsignale auf Bus meldungen (1) starttec-Statuswort 1 starttec Statuswort 1 (C0150) 1 Bit 0 reserviert FIF A FIF-Ausgangswort 1...
  • Page 54 C0055 Scheinstrom Motor 2 Das User-Menü enthält Das User-Menü enthält 3 Speicher 3 C0006 Umschaltung HW/Handterminal in der Lenze-Einstellung in der Lenze Einstellung die wichtigsten Codes 4 Speicher 4 C0120 Motor-Bemessungsstrom für die Inbetriebnahme für die Inbetriebnahme 5 Speicher 5...
  • Page 55: Störungen Erkennen Und Beseitigen

    Slave antwortet nicht. Kommu- Systembus-Konfiguration prüfen nikations-Überwachungszeit überschritten Bei Betrieb mit Modul auf FIF: Rücksprache mit Lenze erforderlich Interner Fehler Externe Störung Ein mit der Funktion TRIP-Set Externen Geber überprüfen E E E E E E E E r r r r...
  • Page 56 Show/Hide Bookmarks Störungen erkennen und beseitigen Störungsmeldungen Anzeige Störung Ursache Abhilfe Keypad PC 252 Fehler in Netzphase Netzphasen an den An- Netzzuleitung phasenrichtig an- E E E E r r r r 2 2 2 2 5 5 5 5 2 2 2 2 schlußklemmen vertauscht schließen (wird nur generiert,...
  • Page 57 PAR1 ist defekt Vor Freigabe unbedingt den Daten- P P P P r r r r 1 1 1 1 tragen transfer wiederholen oder die Lenze- Einstellung laden Interne Störung Rücksprache mit Lenze erforderlich P P P P r r r r 5 5 5 5 Zeitfehler bei Para- Datenfluß...
  • Page 58 Show/Hide Bookmarks This documentation is only valid for starttec motor starters as of version: E71MM402 Type AS-interface _ = not active F = active DC voltage spring-operated brake 2 = 205 VDC 4 = 180 VDC Design x1x = Stand-alone drive x2x = Multi-motor operation, change of direction of rotation Hardware version...
  • Page 59 Show/Hide Bookmarks Quick commissioning ^ 61 Read safety information Mount starttec ^ 71 Ensure minimum wiring 3/N/PE AC 100 … 550 V 45 … 65 Hz +24 V DC (+18 VDC - 0 % … +30 VDC + 0 %, 200 mA ...
  • Page 60 ..........Lenze low-voltage machinery .
  • Page 61: Safety Instructions

    (according to Low-Voltage Directive 73/23/EEC) 1. General Some parts of Lenze motor starters can be live, moving and rotating, depending on their protection class. Surfaces can be hot. Non-authorized removal of the required cover, inappropriate use, incorrect installation or operation, creates the risk of severe injury to persons or damage to material assets.
  • Page 62 Show/Hide Bookmarks Safety instructions Motor starter 5. Electrical connection When working on live motor starters, the applicable national regulations for the prevention of accidents (e.g. VBG 4) must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross-sections, fuses, PE connection).
  • Page 63: Lenze Low-Voltage Machinery

    Show/Hide Bookmarks Safety instructions Lenze low-voltage machinery General safety and application notes for Lenze low-voltage machinery (in conformity with the Low-Voltage Directive 73/23/EEC) 1. General Low-voltage machines have dangerous, live and rotating parts as well as possibly hot surfaces. All operations serving transport, connection, commissioning and maintenance are to be carried out by skilled, responsible technical personnel (observe EN 50110-1 (VDE 0105-100);...
  • Page 64 Show/Hide Bookmarks Safety instructions Lenze low-voltage machinery 5. Electrical connection All operations must be carried out only by qualified and skilled personnel when the low-voltage machine is at standstill and when the machine is de-energized and protected against unintentional restart. This also applies to auxiliary circuits (e.g.
  • Page 65: Residual Hazards, Layout Of Safety Instructions

    Show/Hide Bookmarks Safety instructions Residual hazards, layout of safety instructions Residual hazards Protection of All power connections (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 and BN) can carry persons dangerous voltage when the starttec is connected to the mains. Therefore the starttec must be disconnected before you start working on it or open the housing.
  • Page 66 Show/Hide Bookmarks Safety instructions Residual hazards, layout of safety instructions Layout of safety instructions All safety instructions given in this documentation have the same layout: Pictograph (indicates the type of danger) Signal word (indicates the degree of danger) Note (describes the danger and explains how to avoid it) Signal word Pictograph Pictograph...
  • Page 67: Technical Data

    Show/Hide Bookmarks Technical data General data Conformity Low-Voltage Directive (73/23/EEC) EMC Directive (93/68/EEC) Approvals UL 508 Underwriter Laboratories (File-No. E132659) Power Conversion Equipment (in preparation) Standards DIN EN 60947-4-2 Semiconductor motor control devices and starters for AC voltage Vibration resistance Acceleration resistant up to 4g (Germanischer Lloyd, general conditions) Climatic conditions Class 3K3 to EN 50178 (without condensation, average relative humidity 85...
  • Page 68: Rated Data

    Max. continuous output current 9.5 A (sum of output currents) Cyclic switching max. 1 / s Motor power (Lenze motors) with 3/PE AC 230 V P 0.25 ... 2.2 kW with 3(/N)/PE AC 400 V P 0.25 ... 4.0 kW max.
  • Page 69 0.02 1000 10000 t [s] start031 Class 10A Class 10 = Lenze setting Activation characteristic adjustable under C0121 Activation characteristic adjustable under C0121 Class 20 Class 30 Output current Rated motor current adjustable under C0120 or with step switch Example for class The starttec switches off and sends an error message if the output current I exceeds the rated motor current for approx.
  • Page 70: Dimensions, Mechanical Design

    Show/Hide Bookmarks Technical data Dimensions, mechanical design Dimensions start001 a [mm] b [mm] c [mm] d [mm] e [mm] 228.0 10.0 104.5 129.0 71.0 Mechanical design Housing Cable connections Weight Housing with electronic module from 4 M20 (threaded length 10 mm) aluminium die-cast 6 M16 (threaded length 10 mm) 1.3 kg...
  • Page 71: Delivery Package

    Show/Hide Bookmarks Delivery package -20- start010 Housing with electronic module Housing cover Distance and wall mounting plate Seal Screws KA 50 18 EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 72: Mechanical Installation

    Show/Hide Bookmarks Mechanical installation Motor mounting 3.4 Nm 30 lb-in 68-73mm 4 × 6 × start024 Screw (DIN 7985) 20 mm, max. M5 Serrated lock washer to DIN 6798 EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 73: Wall Mounting

    Show/Hide Bookmarks Mechanical installation Wall mounting 5.3 mm 4 × 6 × 3.4 Nm 30 lb-in start022 Distance and wall mounting plate Drilling pattern Distance a [mm] b [mm] c [mm] d [mm] e [mm] EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 74: Elektrical Installation

    Show/Hide Bookmarks Electrical installation Important notes Danger! -21- All power connections (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 and BN) can carry dangerous voltage when the starttec is connected to the mains. Therefore the starttec must be disconnected before you start working on it or open the housing.
  • Page 75: Connection Diagram

    4 mm (AWG 10) 1U, 1V, 1W Motor 1 connection ^ 77 B1, B2, BN Connection of Lenze spring operated brake BFK457 or BFK458 X3/59 Connection of supply voltage +24 VDC +18 VDC - 0 % ... +30 VDC + 0 %) Reference: X3/7 min.
  • Page 76 Show/Hide Bookmarks Electrical installation Connection diagram Terminal Function (bold = Lenze setting) Data Digital inputs X3/28 X3/28 starttec enable/inhibit starttec enable/inhibit LOW (0 V ... +3 V) LOW (0 V ... +3 V) HIGH starttec enabled HIGH (+12 V ... +30 V) LOW starttec inhibit = >...
  • Page 77: Spring-Operated Brake

    Show/Hide Bookmarks Electrical installation Spring-operated brake Danger! -22- All power connections (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 and BN) can carry dangerous voltage when the starttec is connected to the mains. Therefore the starttec must be disconnected before you start working on it or open the housing. Stop! If you use the starttec for a spring-operated brake, type E71MM402x4Axxx (brake voltage 180 VDC) must only be connected to a ≤...
  • Page 78 Show/Hide Bookmarks Electrical installation Spring-operated brake Connection diagram for starttec E71MM402x2Axxx (motor in * * * * connection, BN conductor from motor star point) Mains 3/PE AC 400 ... 500 V, brake voltage 205 ... 257 VDC Zero potential at star point only from a certain motor voltage on. The brake voltage will then be available. 3/PE AC 400 ...
  • Page 79: As Interface Connection

    Show/Hide Bookmarks Electrical installation AS interface connection Note! The AS interface is only active with starttec type E71MM402FxAxxx! -23- Communication data Protocol / communication medium AS-i Network topology Tree Bus devices Slave Slave profile S-7.F (IO code: 7 , ID code: F Operationg parameters Data structure 3 AS-i data bit (D0, D1, D2) to starttec...
  • Page 80 Show/Hide Bookmarks Electrical installation AS interface connection Configuration Data bits to starttec: Go to C0410 (selection 6, 7, 8) to assign the data bits D0, D1 and D2 to internal digital signals. Data bits from starttec: Go to C0415, subcodes 5 and 6 to assign the data bits D0 and D1 to internal digital signals. Example: The starttec is to be enabled via AS-i and a brake motor is to be started.
  • Page 81: Bus Function Module Connection

    Show/Hide Bookmarks Electrical installation Bus function module connection The starttec can be connected to the following bus systems when using the FIF interface: Bus system Required Lenze FIF module PROFIBUS-DP E82ZAFP 001 INTERBUS E82ZAFI 001 System bus (CAN) E82ZAFC 001...
  • Page 82: Setting Of All Important Parameters

    -24- rated motor current - step switch acceleration time - potentiometer ”T” initial voltage - potentiometer ”U ” Step switch [S] Rated Lenze motor power at mains voltage Note Position Rated current 3/PE AC 3(/N)/PE AC 3(/N)/PE AC 230 V...
  • Page 83: Commissioning

    Show/Hide Bookmarks Commissioning Before switching on Stop! -25- Short circuits or earth faults in the wiring destroy the starttec. Check the wiring for short circuit and earth fault. Damage to persons and material can be avoided by checking Wiring: completeness, earth fault and short circuit. Emergency off function of system Correct setting of rated motor current.
  • Page 84: Without Hand Terminal

    Show/Hide Bookmarks Commissioning Without hand terminal Note! Do not change the switch-on sequence. In the event of an error during commissioning please see the chapter ”Fault detection and elimination”. Switch-on sequence Note Ensure that the starttec is inhibited Terminal X3/28 = LOW after mains switch on.
  • Page 85: With Hand Terminal

    – is active after every mains connection if the hand terminal is already connected or plugged into the AIF interface during operation. – contains all codes required for a standard application (Lenze setting). – can be modified as required under C0517.
  • Page 86 Show/Hide Bookmarks Commissioning With hand terminal Change between the menus u u u u S S S S E E E E r r r r and A A A A L L L L L L L L -27- uSEr Œ...
  • Page 87 (Code C0517) are available immediately. In default setting the menu user contains all codes required for a standard application: Code Name Lenze setting C0054 Apparent motor 1 current Only display C0055 Apparent motor 2 current...
  • Page 88 Show/Hide Bookmarks Commissioning With hand terminal Parameter change in menus Step Keys Display Note Example starttec Only necessary if you want to change codes inhibit marked with s in the code table, e.g.: C0002 All other parameters can be changed during operation.
  • Page 89 C0006 is set PT: Potentiometer ”T” for PT: Potentiometer ”T” for accordingly acco d g y acceleration time acceleration time Lenze setting: -0- S: Step switch for rated motor current H: Hand terminal H: Hand terminal Important Important...
  • Page 90 10. Configuration of digital input signals Linkage of external signal  j g f k i h PS 04 10 sources to internal digital Lenze setting: 00 1 signals C0410/1 = 1: For more settings see the – X3/E1: Motor 1 start/stop...
  • Page 91 Motor 1 start Switch on delay t (C0423) Switch off delay t Switch off delay t (C0424) (C0424) B ff Boff Voltage characteristic at Lenze setting: 0.00 s 1U, 1V, 1W (motor 1)        ...
  • Page 92: Code Table

    S S S S E E E E r r r r u u u u S S S S E E E E r r r r With Lenze setting the code is available in the menu . The menu u u u u S S S S E E E E r r r r is active after every mains switching.
  • Page 93 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0002 Parameter set Parameters can only be transfer using transferred to other the hand starttecs by using the hand u u u u S S S S E E E E r r r r...
  • Page 94 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0006 Changeover Code parameterisation C0012 C0016 C0120 HW/hand HW/hand via: via: U U U U S S S S E E E E r r r r terminal –...
  • Page 95 No current error C0043 C0043 = 0 Active error C0052 Service code Modifications only by Lenze Service! C0054 Apparent motor 50 Only display current 1 u u u u S S S S E E E E r r r r C0055...
  • Page 96 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection Activation characteristic, Activation characteristic, C0121 Activation class see ^ 69 ^ 69 1 Motor 1 Activation class 10 2 Motor 2 Activation class 10 t-monitoring switched off Activation class 10A...
  • Page 97 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0150 starttec status Status query via parameter channel. The Some bits can be linked word 1 most important status information are to internal digital signals (parameter grouped as bit pattern.
  • Page 98 C0164 Last but two fault Modifications only by C0165 Service code Lenze Service! LECOM C0170 Configuration TRIP reset via bus TRIP reset by switching the 24 VDC TRIP reset function module with voltage supply, LOW–transition at C0043, C0410/12 or...
  • Page 99 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0351 C0351 System bus System bus Changes will become Changes will become 500 kbit/s b d t baud rate effective after the ff ti ft th 250 kbit/s command ”reset node”...
  • Page 100 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0356 System bus time settings 3000 0 {1 ms} 65000 Required for CAN network 1 Boot up without master 2 Cycle time 0 and C0360 = 0: CAN-OUT2...
  • Page 101 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0372 C0372 Function Function Only display Only display No function module module System bus (CAN) identification identification other bus function module FIF, e. g. INTERBUS, PROFIBUS-DP, ... No valid recognition 20.00 The digital signal linked...
  • Page 102 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0410 Configuration digital input Linkage of external signal sources signals u u u u S S S S E E E E r r r r to internal digital signals...
  • Page 103 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0410 C0410 External signal sources Not assigned u u u u S S S S E E E E r r r r S S S S E E E E...
  • Page 104 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0415 Digital output signal Output of internal digital signals to configuration u u u u S S S S E E E E r r r r terminals or AS interface...
  • Page 105 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection C0415 Apparent current (C0054) < current Belt monitoring motor 1 threshold (C0156/1) u u u u S S S S E E E E r r r r Apparent current (C0055) <...
  • Page 106 Show/Hide Bookmarks Commissioning Code table Code Possible settings IMPORTANT Name Lenze Selection The assignment is mapped C0417 starttec status to the message configuration starttec status word 1 Output of internal digital signals to bus (C0150) (C0150) 1 Bit 0 Reserved...
  • Page 107 2 Memory 2 C0055 Apparent motor 2 current displayed. displayed. 3 Memory 3 C0006 Changeover HW/hand terminal With Lenze setting, the With Lenze setting, the user menu contains the 4 Memory 4 C0120 Rated motor current codes most important codes most important...
  • Page 108: Troubleshooting

    Check system bus configuration Slave does not respond. Communication monitoring time exceeded Operation with module on FIF: Contact Lenze Internal error External error A digital signal used for the Check external encoder E E E E E E E E r r r r...
  • Page 109 Show/Hide Bookmarks Troubleshooting Error messages Display Fault Cause Remedy Keypad PC 252 Error in mains Mains phase connection to Correct the phase connection E E E E r r r r 2 2 2 2 5 5 5 5 2 2 2 2 phase terminals mixed up (wrong direction of rotation)
  • Page 110 X3/T1 and or switch off monitoring X3/T2 PAR1 transmitted PAR1 is faulty Repeat data transfer or load Lenze P P P P r r r r 1 1 1 1 incorrectly setting before enabling the controller Internal fault...
  • Page 111 Show/Hide Bookmarks Troubleshooting Error messages EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 112 Show/Hide Bookmarks Le présent fascicule s’applique aux démarreurs moteur starttec des versions suivantes : E71MM402 Type Interface AS-i _ = Désactivée F = Activée Tension CC frein à ressorts à manque de courant 2 = 205 VCC 4 = 180 VCC Version x1x = Entraînement individuel x2x = Fonctionnement multimoteurs, inversion du...
  • Page 113 Show/Hide Bookmarks Mise en service rapide ^ 115 Lire les consignes de sécurité. Monter le starttec. ^ 126 Etablir le câblage mini. 3/N/PE AC 100 … 550 V 45 … 65 Hz +24 V DC (+18 VDC - 0 % … +30 VDC + 0 %, 200 mA ...
  • Page 114 ........Démarreurs moteur Lenze .
  • Page 115: Consignes De Sécurité

    Conformes à la directive Basse Tension 73/23/CEE 1. Généralités Selon leur degré de protection, les démarreurs moteur Lenze peuvent avoir, pendant leur fonctionnement, des parties sous tension, éventuellement en mouvement ou tournantes. Les surfaces risquent d’être chaudes. Un enlèvement non autorisé des protections prescrites, un usage non conforme à la fonction, une installation défectueuse ou une manoeuvre erronée peuvent entraîner des dommages corporels et matériels graves.
  • Page 116 Show/Hide Bookmarks Consignes de sécurité Démarreurs moteur Lenze 5. Raccordement électrique Lorsque des travaux sont effectués sur le démarreur moteur sous tension, les prescriptions nationales pour la prévention d’accidents doivent être respectées (par exemple VBG 4). L’installation électrique doit être exécutée en conformité avec les prescriptions applicables (par exemple sections des conducteurs, protection par coupe-circuit à...
  • Page 117: Machines À Courant Triphasé

    Show/Hide Bookmarks Consignes de sécurité Machines à courant triphasé Instructions de sécurité et de mise en service relatives aux machines à basse tension Conformes à la directive Basse Tension 73/23/CEE 1. Généralités Les machines à basse tension comportent des parties dangereuses sous tension et tournantes, ainsi que, le cas échéant, des surfaces chaudes.
  • Page 118 Show/Hide Bookmarks Consignes de sécurité Machines à courant triphasé 4. Installation Assurer une surface d’appui plane, une bonne fixation des pattes, ou selon le cas, des brides, et un alignement précis en cas d’accouplement direct. Eviter que le montage ne provoque des résonances dues à...
  • Page 119 Show/Hide Bookmarks Consignes de sécurité Machines à courant triphasé 6. Fonctionnement ≤ 3,5 mm/s (P ≤ 15 kW) ou 4,5 mm/s (P Des vibrations de vitesse v > 15 kW) respectivement en marche couplé sont sans conséquence. En cas d’écart par rapport au fonctionnement normal - par exemple températures élevées, bruit, vibrations - en rechercher l’origine.
  • Page 120: Dangers Résiduels, Présentation Des Consignes De Sécurité

    Show/Hide Bookmarks Consignes de sécurité Dangers résiduels, présentation des consignes de sécurité Dangers résiduels Protection des Lorsque le starttec est connecté au réseau, toutes les bornes de puissance (L1, L2, personnes L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 et BN) risquent d’être sous tension dangereuse. Mettre le starttec hors tension avant de procéder aux travaux sur le starttec ou d’ouvrir le boîtier.
  • Page 121: Le Mot Associé Au Pictogramme

    Show/Hide Bookmarks Consignes de sécurité Dangers résiduels, présentation des consignes de sécurité Présentation des consignes de sécurité Toutes les consignes de sécurité sont présentées de façon identique : Le pictogramme annonce le type de risque. Le mot associé au pictogramme désigne l’intensité...
  • Page 122: Spécifications Techniques

    Show/Hide Bookmarks Spécifications techniques Caractéristiques générales Conformité Directive Basse Tension (73/23/CEE) Directive CEM (93/68/CEE) Homologations UL 508 Underwriter Laboratories (File-No. E132659) Power Conversion Equipment (en préparation) Normes DIN EN 60947-4-2 Gradateurs et démarreurs à semiconducteurs de moteurs à courant alternatif Résistance aux chocs Résistance à...
  • Page 123: Caractéristiques Nominales

    Courant permanent de sortie maxi 9,5 A (total de tous les courants de sortie) Commutation répétée 1 commutation/s maxi Puissance moteur (moteurs Lenze) sur 3/PE CA 230 V P 0,25 ... 2,2 kW sur 3(/N)/PE CA 400 V P 0,25 ... 4,0 kW...
  • Page 124 1000 10000 t [s] start031 Classe 10A Classe 10 = réglage Lenze Classes de déclenchement réglables en C0121 Classes de déclenchement réglables en C0121 Classe 20 Classe 30 Courant de sortie Courant nominal moteur réglable en C0120 ou à l’aide du gradateur Exemple : Le starttec est désactivé...
  • Page 125: Encombrements, Conception Mécanique

    Show/Hide Bookmarks Spécifications techniques Encombrements, conception mécanique Encombrements start001 a [mm] b [mm] c [mm] d [mm] e [mm] 228,0 10,0 104,5 129,0 71,0 Conception mécanique Boîtier Raccords vissés Poids Embase en aluminium coulé sous pression 4 x M20 (longueur filetée 10 mm) avec module électronique 6 x M16 (longueur filetée 10 mm) 1,3 kg...
  • Page 126: Equipement Livré

    Show/Hide Bookmarks Equipement livré -35- start010 Embase du boîtier avec module électronique Couvercle boîtier Plaque d’écartement/de montage Joint Vis KA 50 18 EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 127: Installation Mécanique

    Show/Hide Bookmarks Installation mécanique Montage sur le moteur 3.4 Nm 30 lb-in 68-73mm 4 × 6 × start024 Vis (DIN 7985) 20 mm, M5 maxi Rondelle à dents chevauchantes selon DIN 6798 EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 128: Montage Au Mur/Sur Le Bâti De La Machine

    Show/Hide Bookmarks Installation mécanique Montage au mur/sur le bâti de la machine 5.3 mm 4 × 6 × 3.4 Nm 30 lb-in start022 Plaque d’écartement/de montage Orifices de perçage Distance a [mm] b [mm] c [mm] d [mm] e [mm] EDK71MMXXX-010 DE/EN/FR 2.0...
  • Page 129: Installation Électrique

    Show/Hide Bookmarks Installation électrique Instructions importantes Danger ! -36- Lorsque le starttec est connecté au réseau, toutes les bornes de puissance (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 et BN) risquent d’être sous tension dangereuse. Mettre le starttec hors tension avant de procéder aux travaux sur le starttec ou d’ouvrir le boîtier.
  • Page 130: Plan De Raccordement

    4 mm maxi (AWG 10) 1U, 1V, 1W Raccordement moteur 1 ^ 132 B1, B2, BN Raccordement frein à manque de courant Lenze BFK457 ou BFK458 X3/59 Raccordement alimentation externe +24 VCC +18 VCC - 0 % ... +30 VCC + 0 %) Référence : X3/7...
  • Page 131 Show/Hide Bookmarks Installation électrique Plan de raccordement Borne Fonction (en gras = réglage Lenze) Données Entrées numériques X3/28 X3/28 Déblocage/blocage du Déblocage/blocage du BAS (0 V ... +3 V) BAS (0 V ... +3 V) HAUT starttec débloqué starttec t tt HAUT (+12 V ...
  • Page 132: Raccordement Frein À Ressorts À Manque De Courant

    Show/Hide Bookmarks Installation électrique Raccordement frein à ressorts à manque de courant Danger ! -37- Lorsque le starttec est connecté au réseau, toutes les bornes de puissance (L1, L2, L3, 1U, 1V, 1W, 2U, 2V, 2W, B1, B2 et BN) risquent d’être sous tension dangereuse. Mettre le starttec hors tension avant de procéder aux travaux sur le starttec ou d’ouvrir le boîtier.
  • Page 133 Show/Hide Bookmarks Installation électrique Raccordement frein à ressorts à manque de courant Plan de raccordement starttec E71MM402x2Axxx (moteur en couplage * * * * , conducteur BN du point neutre du moteur) Réseau 3/PE CA 400 ... 500 V, tension de freinage 205 ... 257 VCC Le potentiel zéro n’est appliqué...
  • Page 134: Raccordement Interface As-I

    Show/Hide Bookmarks Installation électrique Raccordement interface AS-i Nota ! L’interface AS-i n’est activée que sur les starttec type E71MM402FxAxxx ! -38- Spécifications de communication Protocole/support de communication AS-i Topologie du réseau Arborescence Abonné au bus Esclave Profil esclave S-7.F (Code IO : 7 , code ID : F Paramètres de fonctionnement Structure de données...
  • Page 135: Configuration

    Show/Hide Bookmarks Installation électrique Raccordement interface AS-i Configuration Bits de données émis au starttec Les bits de données D0, D1 et D2 peuvent être affectés aux signaux numériques internes en C0410 (réglage possible : 6, 7, 8). Bits de données reçus du starttec Les bits de données D0 et D1 peuvent être affectés aux signaux numériques internes en C0415 (sous-codes 5 et 6).
  • Page 136: Raccordement Modules De Fonction Bus

    Show/Hide Bookmarks Installation électrique Raccordement modules de fonction bus Via interface FIF, le starttec peut être utilisé sur les bus systèmes suivants : Bus système Module FIF Lenze nécessaire PROFIBUS-DP E82ZAFP 001 INTERBUS E82ZAFI 001 Bus système (CAN) E82ZAFC 001...
  • Page 137: Réglage Des Principaux Paramètres

    Réglage Remarque Régler le courant nominal moteur à Voir ^ 124 l’aide du gradateur. Le réglage en C0120 Réglage Lenze : 1 = 1,0 A peut être modifié et vérifié à l’aide du clavier avec boîtier. 3.0 A start032 Régler le temps d’accélération t à...
  • Page 138: Mise En Service

    Show/Hide Bookmarks Mise en service Avant la première mise en service Stop ! -40- Un court-circuit ou une mise à la terre dans le câblage entraîne la destruction du starttec. Vérifier le câblage dans son intégralité afin d’éviter un court-circuit ou un défaut terre.
  • Page 139: Sans Clavier Avec Boîtier

    Show/Hide Bookmarks Mise en service Sans clavier avec boîtier Nota ! Respecter l’ordre des opérations. En cas de problèmes lors de la mise en service, consulter le chapitre ”Détection et élimination des défauts” : Ordre des opérations Remarque S’assurer que le blocage starttec Borne X3/28 = BAS soit activé...
  • Page 140: Clavier Avec Boîtier

    Show/Hide Bookmarks Mise en service Clavier avec boîtier Le clavier avec boîtier E82ZBB et le câble de liaison nécessaire sont disponibles en option. Pour la description complète du clavier avec boîtier, se reporter à la feuille comprise dans l’emballage du clavier.
  • Page 141 Show/Hide Bookmarks Mise en service Clavier avec boîtier Comment passer du menu u u u u S S S S E E E E r r r r à A A A A L L L L L L L L -42- uSEr Œ...
  • Page 142 à l’interface AIF pendant le fonctionnement. En réglage usine, le menu user comprend tous les paramètres d’entraînement pour la mise en service d’une application standard. Code Désignation Réglage Lenze C0054 Courant apparent moteur 1 Seulement en affichage C0055 Courant apparent moteur 2 Seulement en affichage C0006 Changement paramétrage...
  • Page 143: Comment Modifier Les Paramètres

    Show/Hide Bookmarks Mise en service Clavier avec boîtier Comment modifier les paramètres Etape Séquence Affichage Remarque Exemple touches 1. Bloquer le Uniquement nécessaire pour modifier les starttec. codes marqués par s dans le tableau des codes (exemple : C0002) Tous les autres paramètres peuvent être modifiés pendant le fonctionnement.
  • Page 144 PT P t ti PT : Potentiomètre ”T” èt ”T” Réglage Lenze : -0- ég age e e pour le temps pour le temps d’accélération S : Gradateur pour...
  • Page 145 PS 04 10 numériques. signaux externes avec des 00 1 signaux numériques internes Réglage Lenze : Pour d’autres réglages C0410/1 = 1 : possibles, se reporter au start039 – X3/E1 : Démarrage/arrêt tableau des codes. ( ^ 148)
  • Page 146 1W (moteur 1) (C0424)          Réglage Lenze 0 00 s Réglage Lenze : 0.00 s Commande frein sur B1, start014 start014 Courbe de tension de freinage sur B1, B2 CINH CINH CINH CINH...
  • Page 147 Show/Hide Bookmarks Mise en service Clavier avec boîtier Ordre des opérations Remarque Après modification de tous les paramètres souhaités 16. Débloquer le starttec. Borne X3/28 = HAUT 17. Le cas échéant, débloquer le frein. Borne X3/E3 = HAUT 18. Démarrer l’entraînement. Démarrage moteur 1 Borne X3/E1 = HAUT CINH Débloquer le starttec via...
  • Page 148: Tableau Des Codes

    . Le menu actif après chaque mise sous tension. Désignation Désignation du code Lenze Réglage Lenze (valeur disponible à la livraison ou après substitution par le réglage Lenze en C0002) La colonne ”IMPORTANT” contient des informations supplémentaires. à Choix 99 Valeur mini {unité}...
  • Page 149 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0002 Transfert de jeux Le clavier avec boîtier vous de paramètres permet de transférer les via clavier avec paramètres vers un autre u u u u S S S S E E E E r r r r boîtier...
  • Page 150 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0004 Affichage L’affichage graphique {n° code} graphique de de barres indique la barres valeur sélectionnée en % à la mise sous % à la mise sous 54 = courant apparent moteur 1 (C0054) tension.
  • Page 151 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0012 Temps 0.00 {0.01 s} 3.00 Temps de modification de d’accélération tension U ... U u u u u S S S S E E E E r r r r réseau...
  • Page 152: Voir Plaque Signalétique Moteur

    Défaut actif (TRIP-Reset) Modifications C0052 Code service Lenze uniquement par le service Lenze ! C0054 Courant apparent 50 Seulement en affichage moteur 1 u u u u S S S S E E E E r r r r C0055...
  • Page 153 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix Caractéristique de C0121 Classe de déclenchement voir ^ 124 déclenchement voir ^ 124 déclenchement 1 Moteur 1 Classe de déclenchement 10 2 Moteur 2 Classe de déclenchement 10...
  • Page 154 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0135 Mot de Commande du starttec via canal de C0135 ne peut pas être commande données paramètres. Les principales modifié à l’aide du clavier starttec (canal de instructions de commande sont regroupées...
  • Page 155 Désignation Lenze Choix C0150 Mot d’état Interrogation de l’état via le canal de Certains bits peuvent starttec 1 (canal données paramètres. Les principales être reliés avec des de données informations d’état sont regroupées sous signaux numériques paramètres) forme de bit.
  • Page 156 à 3 digits alphanumérique à 3 digits C0164 Avant-avant-der nier défaut Modifications C0165 Code service Lenze uniquement par le service Lenze ! LECOM C0170 Configuration Réarmement défaut Réarmement défaut (TRIP-Reset) TRIP-Reset (TRIP-Reset) par module par coupure et branchement de (réarmement de fonction bus avec l’alimentation 24 VCC, impulsion...
  • Page 157 N° Désignation Lenze Choix Modifications Modifications Codes service Codes service C0304 Lenze uniquement par le service Lenze ! service Lenze ! C0310 C0350 Adresse sur le 63 Modification activée après bus CAN l’instruction ”Reset-Node” (réarmement noeuds) C0351 C0351 Vitesse de Vitesse de Modification activée après...
  • Page 158 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0355 Identificateur bus 2047 Seulement en affichage système Identificateur de CAN1 1 CAN-IN1 avec émission en réponse à un télégramme de à un télégramme de...
  • Page 159 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0359 C0359 Etat bus système Etat bus système Seulement en affichage Seulement en affichage Opérationnel Pré-opérationnel Warning Bus-Off C0360 C0360 Commande Commande Emission événementielle/cyclique canal de Emission en réponse à...
  • Page 160 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0409 Interconnexion logiques des signaux d’entrée numériques 1 E1 1 E1 Non relié E1 ET E4 E1 OU E4 2 E2 2 E2 Non relié...
  • Page 161 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0410 Configuration Interconnexion de sources signaux signaux d’entrée externes avec des signaux numériques u u u u S S S S E E E E r r r r numériques internes...
  • Page 162 Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0410 C0410 Sources signaux externes Non affecté u u u u S S S S E E E E r r r r S S S S E E E E Entrée numérique X3/E1...
  • Page 163 Show/Hide Bookmarks Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0415 Configuration Sortie de signaux numériques signaux de sortie internes sur bornier ou interface numériques u u u u S S S S E E E E r r r r AS-i 1 Sortie numérique...
  • Page 164 Mise en service Tableau des codes Code Réglages possibles IMPORTANT N° Désignation Lenze Choix C0415 Courant apparent (C0054) < seuil Surveillance courroie de courant (C0156/1) moteur 1 u u u u S S S S E E E E r r r r Courant apparent (C0055) <...
  • Page 165 Configuration Sortie des signaux numériques internes sur représentée sur messages d’état starttec (1) le mot d’état starttec 1 le mot d état starttec 1 (C0150), 1 Bit 0 Réservé le mot de sortie FIF 1 i FIF 1 2 Bit 1 Réservé...
  • Page 166 3 Mémoire 3 C000 Changement paramétrage via principaux codes (en matériel/paramétrage via clavier réglage Lenze) pour la avec boîtier mise en service d’une mise en service d une application standard. 4 Mémoire 4 C012 Courant nominal moteur Entrer les numéros des...
  • Page 167: Détection Et Élimination Des Défauts

    Show/Hide Bookmarks Détection et élimination des défauts Messages défauts LEDs sur le starttec (affichages d’états de fonctionnement) -45- Etat de fonctionnement verte rouge ALLUMEE ETEINTE starttec débloqué CLIGNOTE ETEINTE starttec bloqué ETEINTE CLIGNOTE (cycle de 1 s) Défaut actif, contrôle en C0161 Messages défauts sur le clavier ou dans le programme de paramétrage Global Drive Control Affichage...
  • Page 168 L’esclave ne répond pas. Temps Vérifier la configuration bus de surveillance communication système. dépassé En fonctionnement avec module Contacter votre service Lenze. sur FIF : Défaut interne Défaut externe Un signal numérique affecté de Vérifier le codeur externe. E E E E E E E E r r r r (TRIP-SET) la fonction ”mise en défaut”...
  • Page 169 Lenze. Défaut interne Contacter votre service Lenze. P P P P r r r r 5 5 5 5 Défaut de temps Le transfert des données en Avant le déblocage, renouveler...