08.03 LIMIT WORD
Update notice
Limit word.
Bit
Name
0
EXTERNAL
PLIM
1
CURRENT
PLIM
2
CAP REF
LIMIT
3
IND REF LIMIT 1
4
DC REF MAX
LIM
5
Q CUR LIM
6
GRID POW
LIM
7
DC POW LIM
8
POW FREQ
LIM
9
GRID FILT
POW LIM
10
HIGH UAC
PLIM
11
MPPT PLIM
12
START POW
LIM
Value Description
1
An external active power
limit in MCP parameter
31.16 POWER LIMITING is
limiting the active power.
1
An internal current limit is
limiting the active power.
The limit depends on the
measured ambient
temperature.
1
Capacitive current
reference above limit (24.22
IQ CAP LIMIT)
Inductive current reference
above limit (24.23 IQ IND
LIMIT)
1
02.05 DC REF Q-CTRL is
above the maximum DC
voltage reference.
1
Reactive current is limited
because 01.06 LINE
CURRENT has reached the
maximum allowed current.
1
Instantaneous active power
limitation
1
Active power from the grid
is limited.
1
Active power to the grid is
limited because of grid
overfrequency.
1
Active power to the grid is
limited.
1
Maximum active power is
limited by grid overvoltage.
1
Maximum active power
increase rate is limiting the
active power.
1
Active power ramp-up after
the start is limiting the active
power.