In the configuration of the contact Energy boost or System enable, the display shows
The parameter can possess a value included between -5 and +5.
With value PI = 0, the inlet works from SYSTEM ENABLE.
When the contact opens, the air conditioner is forced in stand-by mode.
When the contact closes, the air conditioner restores the previous operating status.
With value PI ≠ 0, the inlet works from ENERGY BOOST.
Values <0 reduce the Tset in cooling, increasing machine power (for instance, if
Tset=24°C and Energy boost = -3°C, the machine works as if the Tset is 21°C)
Values >0 increase the Tset in heating, increasing machine power (for instance, if
Tset=24°C and Energy boost = 3°C, the machine works if the Tset is 27°C)
To configure the appliance at the activation of one of the two functions, proceed as
follows:
a.
Raise the air intake grille (3) and remove the two screws (3a) (fig. 25).
b.
Extract the right (unlock with a screwdriver) and left (1a) doors of the front cover,
then rotate the flap (1) and remove the three screws (1b) (fig. 28).
c.
Remove the front cover.
d.
Undo the two fixing screws (X2) to remove the front cover of the switchgear (X1)
(fig. 27).
e.
From the screw clamp (Y2), remove the supplied bridge (Y3) (fig. 29).
f.
Close the switchgear.
g.
Reassemble the front cover of the machine.
The inlet must be driven by a potential-free contact.
Do not use a cable longer than meters 10.
2.6.3 - I nput setting configuration
In the configuration of the open or closed contact, the display shows
To set the desired configuration, carry out the previously described procedures and
choose between the parameter
2.6.4 - T emperature unit of measurement configuration
In the configuration of the unit of measurement of temperature, the display shows
To set the desired configuration, carry out the previously described procedures and
choose between the parameter
2.6.5 - H eat pump / only cooling / only heating configuration
During configuration of the mode of operation of the unit, the display shows
To set the machine so as that it works both in cooling and in heating mode, select the
"HP" configuration (heat pump).
EN - 28
(closed contact) or
(metric system) or
.
(open contact).
(imperial system).
.
.
.