Hinweise zur UL Zulassung
de
5.3
Hinweise zum Anschließen
10
B E T R I E B S A N L E I T U N G | GTB20
UL approval
Tabelle 2: UL approval
G20 products with DC voltage supply and with:
•
connector
•
cable
•
cable with connector
UL:
The device shall be supplied from an isolating
transformer having a secondary overcurrent
protective device that complies with UL 248 to
be installed in the field rated either:
a) max 5 amps for voltages 0 V ~ 20 V (0 V ~
28.3 V peak), or
b) 100 / Vp for voltages of 20 V ~ 30 V (28.3
V ~ 42.4 V peak)
Alternatively, they can be supplied from a
Class 2 voltage supply.
UL Environmental Rating: Enclosure type 1
For use in NFPA 79 Applications only
G20 products with AC voltage supply and with:
•
cable
•
cable with connector
UL:
UL Environmental Rating: Enclosure type 1
For use in NFPA 79 Applications only
G20 products with DC and AC/DC voltage sup‐
ply and with:
•
terminal chamber: Gxx20x-QK and Gxx20x-
QL
UL:
For use in NFPA 79 Applications only
Die Sensoren müssen in spannungsfreiem Zustand angeschlossen werden. Je nach
Anschlussart sind die folgenden Hinweise zu beachten:
–
Steckeranschluss: Anschlussbelegung
–
Leitung: Aderfarbe
–
Klemmenanschluss: Anschlussbelegung und die folgenden Punkte
Klemmenanschluss:
1.
Schraube M3 an der hinteren Abdeckung lösen und Rückseite abnehmen.
2.
Spannungsfreie Versorgungsleitung in der richtigen horizontalen oder vertikalen
Position durch MPT-Fassung 3/8" (Außengewinde), Abstandshalter, Gummidich‐
tung (wie unten dargestellt) und Öffnung der hinteren Abdeckung führen.
3.
Die MPT-Fassung 3/8" (Außengewinde) nach
4.
Die einzelnen Adern an der Anschlussleiste anschließen und mit einem Drehmo‐
ment von 0,4 bis 0,5 Nm festziehen
5.
Die Rückwand wieder installieren. Sicherstellen, dass die Rückwand frei von Hin‐
dernissen und fest angezogen ist.
Tabelle 3
und
Tabelle 4
(siehe Tabelle 5, Seite 12
und
8026846.1LP5/2024-05-06 | SICK
Irrtümer und Änderungen vorbehalten
festziehen.
Tabelle
9).