Télécharger Imprimer la page

baltur BGN 40 LX-V Mode D'emploi page 37

Publicité

Les langues disponibles
  • FR

Les langues disponibles

LOW-PRESSURE GAS SUPPLY SYSTEM (max. 400 mm.W.C.)
After having correctly applied the burner to the boiler, it must be connected to the gas pipes (see BT 8819). A suitable
pipe fitting must be installed on these pipes, close to the burner, so as to allow an easy dismantling of the burner and/
or the opening of the boiler port. The following must also be installed: ball stop cock, gas filter and vibration-
damping joint. Said components must be installed as shown in our drawing.
The gas supply pipes must be sized according to the gas length and feed, and they must be perfectly sealed and
properly tested before carrying out the burner general test and inspection. We suggest that you follow the recommen-
dations below relating to the installation of the necessary accessories on the gas pipes close to the burner.
1) The gas filter must be arranged on a horizontal piping, so as to prevent possible impurities from entering into
the piping during the cleaning of the same.
2) It is advisable to install an elbow directly on the burner gas train before applying the removable union. This
allows opening the boiler port after opening the same union. What said above is clearly shown in the following
drawing.
Note: If the burner is equipped with gas valves, model SKP 70 ....., the pressure regulator needs not be installed
since in its normal operation the above valve also functions as pressure regulator.
GENERAL DIAGRAM FOR INSTALLATION OF GATE - FILTER
ANTIVIBRATION JOINT OPENABLE PITTING
UPPER VIEW
Anti-vibration joint
Boiler
Door
Burner
Door opening
direction
Pipe fitting
SIDE VIEW
Gate
Filter
N° BT 8819
37

Publicité

loading