1)
Keypad
PC
Error
64
Communication error to
c c c c e e e e 3 3 3 3
CAN-IN1 with event or
time control
65
BUS-OFF
c c c c e e e e 4 4 4 4
(many communication
faults occurred)
66
CAN Time-Out
c c c c e e e e 5 5 5 5
(configurable in C0126)
67
Function module
c c c c e e e e 6 6 6 6
system bus (CAN) on
FIF has set "Warning"
or "BUS-OFF"
(configurable in C0126)
68
Communication fault
c c c c e e e e 7 7 7 7
during remote
parameter setting via
system bus (C0370)
(configurable in C0126)
91
External fault
E E E E E E E E r r r r
(TRIP-SET)
-
Communication abort
E E E E r r r r P P P P 0 0 0 0
between keypad and
. . . . . . . . . . . .
basic device
E E E E r r r r P P P P 1 1 1 1 9 9 9 9
E82ZMV fan module
95
F F F F A A A A n n n n 1 1 1 1
(only 8200 motec
3 ... 7,5 kW)
3 ... 7,5 kW)
TRIP or warning
-
F F F F A A A A n n n n 1 1 1 1
configurable under
C0608
105
Internal fault
H H H H 0 0 0 0 5 5 5 5
L
All manuals and user guides at all-guides.com
Cause
CAN-IN1 object receives faulty data or
communication is interrupted
Controller has received too many
incorrect telegrams via the system
bus and has been disconnected
For remote parameter setting via
system bus (C0370):
Slave does not answer.
Communication monitoring time
exceeded.
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
For operation with module in FIF:
Internal fault
CAN controller sets "Warning" or "BUS
OFF"
Participant does respond or is not
available
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
A digital input assigned to the
TRIP-Set function has been activated.
Various
Fan module is defect
Fan module is not connected
Remedy
Plug-in connection - bus module
Check FIF
Check transmitter
Increase monitoring time under C0357/3
if necessary
Check whether bus terminator available
Check screen contact of the cables
Check PE connection
Check bus load, if necessary, reduce the
baud rate
Check system bus wiring
Check system bus configuration
In all parameter sets the signal "parameter
set changeover" (C0410/13, C0410/14)
must be combined with the same source
Contact Lenze
Check whether bus terminator available
Check screen contact of the cables
Check PE connection
Check bus load, if necessary, reduce the
baud rate
Check whether bus terminator available
Check screen contact of the cables
Check PE connection
Check bus load, if necessary, reduce the
baud rate
In all parameter sets the signal "parameter
set changeover" (C0410/13, C0410/14)
must be combined with the same source
Check external encoder
Contact Lenze
Replace fan module
Connect fan module
Check wiring
Contact Lenze
9