2
Nr.
Bezeichnung
DE
1
Supply
2
Pt1000 V1
3
Pt1000 V2
4
CAN-Bus 1 Schirm
5
CAN-Bus 1
6
CAN-Bus 2 Schirm
7
CAN-Bus 2
8
DIO-Schnittstelle
9
USB-Schnittstelle
10
Flachbandstecker
Hinweis! Die KHS Hygienespülung PRO besitzt einen potenzialfreien Störmeldekontakt,
der stromlos geöffnet ist, also eine Störung ausgibt.
No. Designation
EN
1
Supply
2
Pt1000 V1
3
Pt1000 V2
4
CAN bus 1 screen –
5
CAN bus 1
6
CAN bus 2 screen –
7
CAN bus 2
8
DIO interface
9
USB interface
Flat ribbon con-
10
nector
Note! The KHS Hygiene Flush Box PRO has a dry contact (NOC) for alarm messaging.
Elektrisch anschließen · Connect to mains power · Effectuer le raccordement
électrique · Collegare all'impianto elettrico · Elektrisch aansluiten
Klemme
Beschriftung
Platine
1
L
2
PE
3
N
1
Ta1
2
Ta2
3
Tb1
4
Tb2
1
Ta1
2
Ta2
3
Tb1
4
Tb2
–
–
1
CAN-L
2
CAN-H
–
–
1
CAN-L
2
CAN-H
1
IN GND
2
IN Flush
3
OUT Flush
4
OUT Alarm
5
OUT COM
–
–
–
–
Terminal
Lettering
on board
1
L
2
PE
3
N
1
Ta1
2
Ta2
3
Tb1
4
Tb2
1
Ta1
2
Ta2
3
Tb1
4
Tb2
–
1
CAN-L
2
CAN-H
–
1
CAN-L
2
CAN-H
1
IN GND
2
IN Flush
3
OUT Flush
4
OUT Alarm
5
OUT COM
–
–
–
–
Beschreibung
Versorgungsspannung Außenleiter
Versorgungsspannung Schutzleiter
Versorgungsspannung Neutralleiter
Temperatursensor Ventil 1 (links) Aderfarbe weiß
Temperatursensor Ventil 1 (links) Aderfarbe weiß
Temperatursensor Ventil 1 (links) Aderfarbe rot
Temperatursensor Ventil 1 (links) Aderfarbe rot
Temperatursensor Ventil 2 (rechts) Aderfarbe weiß
Temperatursensor Ventil 2 (rechts) Aderfarbe weiß
Temperatursensor Ventil 2 (rechts) Aderfarbe rot
Temperatursensor Ventil 2 (rechts) Aderfarbe rot
Schirmklemme (links)
CAN-Bus Ader Low (links)
CAN-Bus Ader High (links)
Schirmklemme (rechts)
CAN-Bus Leitung (rechts)
CAN-Bus Leitung (rechts)
Spülsignal Masse
Spülsignal
Schließerkontakt Potentialfreier Ausgang Spülmeldung <= 24V AC/DC, <= 0.5A
Öffnerkontakt Potentialfreier Ausgang Störmeldung
Gemeinsamer Kontakt der Ausgänge
–
–
Description
Supply voltage line conductor
Supply voltage protective earth conductor
Supply voltage neutral conductor
Temperature sensor valve 1 (left), wire colour white
Temperature sensor valve 1 (left), wire colour white
Temperature sensor valve 1 (left), wire colour red
Temperature sensor valve 1 (left), wire colour red
Temperature sensor valve 2 (right), wire colour white 1000 Ohms at 0°C
Temperature sensor valve 2 (right), wire colour white 1000 Ohms at 0°C
Temperature sensor valve 2 (right), wire colour red
Temperature sensor valve 2 (right), wire colour red
Shield clamp (left)
CAN bus wire Low (left)
CAN bus wire High (left)
Shield clamp (right)
CAN bus cable (right)
CAN bus cable (right)
Spülsignal Masse
Flushing signal
NC Dry contact outlet flushing message
NO Dry contact outlet fault message
Mutual contact of the outputs
–
–
© www.kemper-group.com – 07.2023 / K410068903016-00 – 65 /108
phys. Größe
230V AC
–
0V
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
1000 Ohm bei 0 °C
–
120 Ohm Wellenwiderstand
120 Ohm Wellenwiderstand
–
120 Ohm Wellenwiderstand
120 Ohm Wellenwiderstand
0V
24V
<= 24V AC/DC, <= 0.5A
<= 24V AC/DC, <= 0.5A
–
–
Phys. size
230V AC
–
0V
1000 Ohms at 0°C
1000 Ohms at 0°C
1000 Ohms at 0°C
1000 Ohms at 0°C
1000 Ohms at 0°C
1000 Ohms at 0°C
–
120 Ohms wave impedance
120 Ohms wave impedance
–
120 Ohms wave impedance
120 Ohms wave impedance
0V
24V
<= 24V AC/DC, <= 0.5A
<= 24V AC/DC, <= 0.5A
<= 24V AC/DC, <= 0.5A
–
–