EN
1.4
Trap
PRO controller
Note!
CAN bus connection only in conjunction with
KHS Mini Control System MASTER 2.1
22 /108 – K410068903016-00 / 07.2023 – © www.kemper-group.com
Function
Connection CAN bus:
Fig. 686 02 008
During a fl ushing cycle, the drained water collects in the trap up to
the water trap height. The trap is closed on the waste-water side by
a removable anti-siphon trap cap. A built-in fl oat switch protects the
trap against overfl ow.
The trap cover closes the trap and serves as a splash guard. Un-
derneath is a grid that catches falling objects, for example during
maintenance.
The PRO version of the controller can only be operated via the
integrated web server. The V1 and V2 LEDs serve as status indicators
for the respective water exchange group. When the "PRESS" button
(bottom right) is held for 5 seconds, a local WLAN is established for
10 minutes to connect to a smartphone, tablet or PC. Subsequently,
interval, time, volume and temperature fl ushes can be set using the
integrated commissioning wizard.
Danger! Electricity!
We advise connecting an 0.03-A residual-current device
upstream for personal protection.
Info!
PRO status lights
Status
green
In function
fl ashing green
Wi-Fi active
yellow
CAN bus active
fl ashing yellow
CAN bus + Wi-Fi active
magenta
Update
white
Reset
V1 / V2
green
Standby
blue
Flushing active
red
Error
orange
Warning
red & blue
Flushing active and current error