SAFETY DEVICES
Photocells
Confi gure contact CX or CY (NC), safety input for photocells.
See CX input functions (Function F2) or CY (Function F3) in:
- C1 reopening during closing. When the gate is closing, opening the contact triggers the inversion of movement
until the gate is fully open again;
- C2 close back up during opening. When the gate is opening, opening the contact triggers the inversion of
movement until the gate is completely closed.
- C3 partial stop. Stopping of the gate, if it is moving, with consequent automatic closing (if the automatic closing
function has been entered);
- C4 obstruction wait. Stopping of the gate, if it is moving, which resumes movement once the obstruction is
removed.
If contacts CX and CY are not used they should be deactivated during programming.
10 TS 2 CX CY
10 TS 2 CX CY
1 2 3P 7
1 2 3P 7
FC FA F
FC
-
+
-
-
RX
TX
RX
TX
TX 2
10 2 TX C
NC
TX 2
+ - NO C
NC
+
TX 2
-
DELTA-S
DIR
DELTA
Sensitive Safety Edges
Confi gure contact CX or CY (NC), safety input for sensitive safety-edges.
See CX input functions (Function F2) or CY (Function F3) in:
- C7 reopening during closing. When the gate is closing, opening the contact triggers the inversion of movement
until the gate is fully open again;
- C8 reclosing during opening. When the gate is opening, opening the contact triggers the inversion of movement
until the gate is fully closed.
If contacts CX and CY are not used they should be deactivated during programming.