From this new page you can manage:
• Mot. Spd.
To set MIN and MAX speed on the 2 fans.
• Setp Byp
"Bypass" mode activates based on the temperature:
"Setp Byp" is selectable in a range between 15°C and 30°C
(default 18°C).
• No Frost
From "INSTALL" menu, selecting "NO FROST", you can enter
the "NO FROST" setting menu. From this new page, it is now
possible to choose the desidered function during the "NO
FROST" process. For more details on setting "NO FROST"
functions, see "NO FROST' page.
• Lifetime
To set the filter duration time, which can vary between 3, 6 and
12 months.
• Language
Language selection.
• Modbus ID
In the presence of another installed remote HMI user interface,
you can configure a different address than the default one
(which is "160").
• POSTHEAT
The variable that controls activation of the post-heater, if present.
The editable default value is: YES.
• POSTTEMP
The variable that defines the threshold temperature value, over
which the post-heater switches on, if present. The editable default
value is: 16°C.
UN - BALAN.
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]