從菜單23進入" modbus"子菜單,以編輯與RS485#2相關的以下參數:
從站地址:從1到254,默認為1
Baud Rate: 9600/19200, default 19200
Parity: NONE
指令
Read Coil (Function Code = 01 )
Read Holding Registers (Function Code = 03 )
Read Input Register (Function Code = 04 )
Write Multiple Coils (Function Code =15 )
Write Multiple Holding Registers (Function Code = 16 )
參數圖
VARIABLE
TYPE
ON/OFF
BOOL
OPERATING SPEED
16BIT-INT
SETPOINT 1 TEMPERATURE
16BIT-INT
(SP1) - BYPASS
SETPOINT 2 TEMPERATURE
16BIT-INT
(SP2) - POSTHEATER
SUPPLY SPEED 1 (V1S)
16BIT-INT
SUPPLY SPEED 2 (V2S)
16BIT-INT
SUPPLY SPEED 3 ((V3S)
16BIT-INT
SUPPLY SPEED 4 ((V4S)
16BIT-INT
(SE ESISTENTE)
EXHAUST SPEED 1 (V1H)
16BIT-INT
EXHAUST SPEED 2 (V2H)
16BIT-INT
EXHAUST SPEED 3 (V3H)
16BIT-INT
EXHAUST SPEED 4 (V4H)
16BIT-INT
TIME PERIOD ENABLE
BOOL
MINIMUM PERMITTED
16BIT-INT
SPEED (VMIN)
MAXIMUM PERMITTED
16BIT-INT
SPEED (VMAX)
RELATIVE HUMIDITY HR% 16BIT-INT
AIR QUALITY VOC
16BIT-INT
TEMPERATURE NTC 1
16BIT-INT
TEMPERATURE NTC 2 (EST) 16BIT-INT
TEMPERATURE NTC 3
16BIT-INT
TEMPERATURE NTC 4
16BIT-INT
ACTIVE BYPASS
BOOL
ACTIVE NOFROST
BOOL
ACTIVE POSTHEATER
BOOL
ALARM PRESENCE
16BIT-INT
PERMITTED VALUES
READ/WRITE
TRUE, FALSE
W/R
1,2,3,4
W/R
15 ÷ 30
W/R
10 ÷ 25
W/R
VMIN ÷ V2S
W/R
V1S ÷ V3S
W/R
W/R
V2S ÷ V4S
V3S ÷ VMAX
W/R
VMIN ÷ V2H
W/R
V1H ÷ V3H
W/R
V2H ÷ V4H
W/R
V3H ÷ VMAX
W/R
TRUE, FALSE
W/R
0 ÷ VMAX
R
VMIN ÷ 100
R
0 ÷ 100
R
0 ÷ 100
R
-40 ÷ 60
R
-40 ÷ 60
R
-40 ÷ 60
R
-40 ÷ 60
R
TRUE,FALSE
R
TRUE,FALSE
R
TRUE,FALSE
R
(*)
R
ADDRESS
16399
16400
16401
16402
16403
16404
16405
16406
16407
16408
16409
16410
16411
8961
8964
8974
8975
8976
8977
8978
8979
8981
8982
8983
8984