INSTALLATIoN
Description
3. Description
Up to two heat pumps are connected to a WPM heat pump
manager in a heat pump cascade. Up to six heat pumps can
be connected in conjunction with heat pump extension WPE.
The connection between heat pump manager and heat pump
is carried out via CAN bus. The connection can have a line or
star topology.
3.1
Conditions
- Heat pump must be cascade compatible
- Heat pumps of the same type without an integral WPM
(outputs may be different)
- No hydraulic module in the heating system
- WPMsystem
3.2 Function
- In heating mode, the heat pumps are controlled so that
the compressors have approximately the same number of
hours run.
- The heat pump responsible for DHW heating is the first
heat pump in the cascade. DHW heating is always started
and ended by the first heat pump in the cascade. Addi-
tional heat pumps may provide DHW heating back-up.
- An integral electric emergency/auxiliary heater (NHZ/
DHC) in the heat pump does not have any function in a
cascade.
- If priority operation is activated and the first heat pump
fails, the heat pump cascade is disabled.
Parameter
SETTINGS / DHW / STANDARD SETTING / DHW MoDE / PRI-
oRITY oPERATIoN
Air source heat pumps
- If partial priority operation is activated, a simultaneous
demand for heating or cooling and DHW can be met.
Parameter
SETTINGS / DHW / STANDARD SETTING / DHW MoDE /
PARTIAL PRIoRITY
4. Electrical connection
f Use a screened cable (e.g. J-Y 2x2x0.8 mm²) for the bus
connection.
f Connect the screen at one end.
4.1
Connecting a heat pump to heat pump
manager WPM or heat pump extension
WPE
f Connect the heat pump bus to one of the following termi-
nals (see chapter "Wiring diagram").
Connection
appliance
X1.1
WPM
X1.19
WPM
X3.1
WPE
X3.19
WPE
Example:
Heat pump
BUS
+
-
L
H
4.2 Connecting heat pump extension WPE to
f Connect a free terminal on the WPM to a free terminal on
the WPE (see chapter "Wiring diagram").
Connection
X1.1
X1.19
X3.1
X3.19
Example:
WPM
X1.19
+
-
L
H
4.3 Connecting remote control FET to heat
4.3.1 Required connection when connecting remote
f Connect a free terminal on the WPM to a free terminal on
the WPE.
Connection
X1.2
X1.18
X3.2
X3.18
Example:
WPM
X1.18
+
-
L
H
Transmission
[kbit/s]
20
20
20
20
Do not connect
GND
a
Low
a
High
a
heat pump manager WPM
appliance
WPM
WPM
WPE
WPE
Do not connect
GND
a
Low
a
High
a
pump manager WPM or heat pump
extension WPE
control FET to heat pump extension WPE
appliance
WPM
WPM
WPE
WPE
Do not connect
GND
a
Low
a
High
a
WPM
X1.1
+
Do not connect
-
GND
L
Low
H
High
Transmission
[kbit/s]
20
20
20
20
WPE
X3.1
+
Do not connect
-
GND
L
Low
H
High
Transmission
[kbit/s]
50
50
50
50
WPE
X3.2
+
Do not connect
-
GND
L
Low
H
High
| 9